GENER
AL INFORMA
TION
PR
ODUC
T INFORMA
TION
SY
STEM DESIGN
INTEGR
ATION INT
O SY
STEM
ORDERING INFORMA
TION
EMC installation
EMC remediation
To pass EMC class A, for the above models, ferrite
cores (4pcs) need to be added on both the power
lines and the earth line, in addition, a knot has
to be tied on each line. Ferrite core is a common
anti-interference component in electronic
circuits, which helps to reduce electromagnetic
interference at different frequency.
Ferrite core: each line should snatch one turn on it.
Ferrite cores should be as close as possible to the drive.
Mechanical dimension
The dimension of the ferrite core depends on the
actual cable size, which should be specified by
the OEM depending on the unit design, ambient
temperature, the wire material, current, etc. The
table below is a recommendation.
Wire sizes
Mechanical dimension [mm / inch]
AWG
mm
2
ID
OD
T
6
16
30 / 1.18
50 / 1.97
20 / 0.79
8
10
19 / 0.75
31.5 / 1.24
12.5 / 0.49
10
6
19 / 0.75
31.5 / 1.24
12.5 / 0.49
12
4
19 / 0.75
31.5 / 1.24
12.5 / 0.49
U V W Ground
SY
STEM DESIGN
21
AB237586440343en-000601