EMC installation
EMC best practices
• Use screened (shielded) cables for motor, control
wiring and communication.
• Separate cables for input power, motor wiring
and control wiring. Failure to isolate power,
motor, control and communication cables
can result in unintended behavior or reduced
performance. Minimum 200 mm (7.9 in)
clearance between power, motor and control
cables is required.
• Ensure VFD proper grounding
• Motor cables should be as short as possible to
reduce noise level and leakage currents.
• Use the decoupling plate to fix and terminate
cables (Refer to
EMC correct installation of an
frequency drive CDS303)
• Add ferrite cores on power lines and earth line if
necessary to pass EMC class A.
EMC correct installation
of an frequency drive
CDS303
PLC etc.
Panel
Grounding rail
Decoupling plate
Cable insulation
stripped
All cable entries in
one side of panel
Motor cable
Motor, 3 phases and
protective ground
Reinforced protective ground
L1
L2
L3
PE
Mains supply
Control cables
PLC
Min. 0.025 in ²
(16 mm²)
Equalizing cable
Min. 7.9 in
(200 mm)
between control
cables, motor cable
and mains cable
EMC qualification reports are available upon request to Danfoss technical support.
Compressor
CDS303 drive
Remediation (ferrite cores)
Power size
Voltage
RFI filter
Drive input
Material: manganese zinc ferrite core
Drive output
Material: nickel zinc ferrite core
VZH052CJ
11kW
T2
H2
-
Y
VZH052CG
11kW
T4
H2
Y
Y
VZH065CG
11kW
T4
H2
Y
Y
VZH065CG
15kW
T4
H2
Y
Y
VZH065CG
15kW
T4
H3
-
-
EMC remediation
For some models, ferrite cores need to be added
to the input and/or output of CDS303 drive, as a
remediation, to fulfil the Class A Group 1 emission
and immunity requirements.