Troubleshooting
Check alarm #
#14
#A45
# resistance < 500 KΩ
# resistance > 500 KΩ
Power OFF the unit
Earth
(ground) fault
Earth
(ground) fault
Disconnect power
cable at compressor
electrical box
Perform an insulation
resistance test on the
compressor with
'megger' tester. 500V
Replace compressor and return it for
inspection if under warranty
Replace drive and return it for inspection
if under warranty
Danf
os
s
cc
-000222
Check alarm #
#68
#36
#38
#
Mains failure
Alarm remaining
Internal fault
Others
Safe stop
activated by HP
(High Pressure)
switch trip
Reset high
pressure switch
and Reset the
drive.
Power
shortage while
compressor
was running.
Check the code
number
associated (refer
to the Operating
Instructions)
Return the drive
for inspection
Probably not
a drive nor
compressor
problem
Probable that the
drive must be
returned for
inspection if
under warranty
Power OFF /
power ON the
drive
Check unit main
power supply (for
example other
unit connected
on same power
supply creating
voltage drop at
start)