Technical specifications
Compressor
specifications
Frequency converter
specifications
Compressor
model
Swept volume
Displacement
Oil charge
Net weight
1800 rpm
3000 rpm
3600 rpm
6600 rpm
(cm³/rev) (cu.in/rev) (m³/h) (cu.ft/h) (m³/h) (cu.ft/h) (m³/h) (cu.ft/h) (m³/h) (cu.ft/h)
(dm
3
)
(oz)
(kg)
(lbs)
VLZ065
65.1
4.0
7.0
249
11.7
413
14.1
498
25.8
911
1.57
53
35
77
Mains supply voltage
T4: 380 - 480 V ±10% (3-phase)
Supply frequency
50 / 60 Hz
Output voltage
0 - 100 % of supply voltage
Inputs
4 digital (0-24V), 2 analog (0/±10V or 4-20mA, scalable)
Programmable outputs
2 analog (0/4-20mA) or 2 digital (0-24V)
Protection functions
Over-current protection, low / high current handling
Compressor functions
Motor protection, compressor ramp up/down control
POE
R448A & R449A
R404A
The POE oil RL46HB(215PZ) is an ISO VG 46
synthetic polyol ester (POE) lubricant formulated
specifically for use in refrigeration and air
conditioning compressors using HFC refrigerants.
This product provides effective wear protection
for steel and aluminum surfaces for increased
system life and improved efficiency and is
suitable for both initial fill and service fill. The
combination of low temperature characteristics
and unparalleled chemical and thermal stability
enable the use of RL46HB over a wide operating
temperature range.
R448A and R449A are two HFO-based
refrigerants with similar properties. Both have a
GWP below 1500 and comply with the EU F-gas
regulation.
They can be used as alternatives to R404A
refrigerants in MBP application.
R448A&R449A have zero ozone depletion
potential (ODP = 0). R448A&449A are especially
suitable for low evaporating temperature
applications but they can also be applied to
medium evaporating temperature applications.
R448A &449A are mixtures and have big
temperature glide, and therefore must be
charged in their gas phase.
R404A is an HFC refrigerant. R404A has zero
ozone depletion potential (ODP = 0). R404A is
also suitable for low evaporating temperature
applications but it can also be applied to medium
evaporating temperature applications. R404A is a
mixture and has a very
small temperature glide, and therefore must be
charged in its liquid phase, but for most other
aspects this small glide can be neglected.
Because of the small glide, R404A is often called a
near-azeotropic mixture.
Designation
Composition
ODP
GWP
Safety
group
Boiling
temp °C
Temp
glide °C
Critical
temp °C
Critical
pressure
bar
Cond temp
@ 26babs
R404A
52% R143a - 44% R125 - 4% R134a
0
3943
A1
-45.5
0.8
73.0
36.9
55.8
R448A
21% R134a - 20% R1234yf
26% R125 - 26% R32 - 7% R1234ze
0
1273
A1
-46.1
6.1
83.7
48.0
58.1
R449A
24.3% R32 - 24.7% R125
25.3% R1234yf - 25.7% R134a
0
1282
A1
-45.7
6.0
83.9
44.5
58.2
8
AB444226142054en-000101
Содержание VLZ065
Страница 2: ......
Страница 53: ...53 AB444226142054en 000101...