Manage operating envelope
Protection required
• HP switch*
• LP switch*
• DGT set @ 135°C (275°F) if necessary
see §Discharge T° protection
•Measurements of suction and discharge pressure,
unit controller is permanently maintaining compressor
within its envelope
with right minimum speed
•drive setting:
parameter 4-11[ Motor speed low limit(rpm)]: keep
default value as 1800
See “Test, criteria and solutions”
OE-000067
3000-6600RPM
HP switch setting
MOP
1800-6600RPM
Condensing pressure control
Minimum pressure ratio
LP switch setting
3300-6600RPM
DGT
Multiple envelope control: Speed range <3000 allowed
Test N°
Purpose
Test condition
Pass criteria
Solutions
1
Check reaction
of system to oil
boost
Stabilized the system in area below
minimum speed (2400RPM) until oil
boost happen
No unsafties happen
Superheat requirement fulfilled
Modify ramp-up
Modify superheat control
Controller needs to manage speed limitation
according to operating conditions.
Below 2400RPM oil boost function is disabled
by default but could be enabled by OEM (more
details
“Oil management logic”
)
*for more details see “Control Logic”
31
AB444226142054en-000101