Frequency converter, P18K, T2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
36
240
0.244
0.608
1.993
136
240
0.568
0.580
0.832
150
240
0.720
0.574
0.661
Table 8.13
Frequency converter, P22K, T2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
36
240
0.244
0.608
1.993
136
240
0.560
0.580
0.832
150
240
0.720
0.574
0.661
Table 8.14
Frequency converter, P30K, T2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
15
240
0.194
0.626
2.581
50
240
0.252
0.574
1.929
150
240
0.444
0.538
0.977
Table 8.15
Frequency converter, P37K, T2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
240
0.300
0.598
1.593
100
240
0.536
0.566
0.843
150
240
0.776
0.546
0.559
Table 8.16
Frequency converter, P45K, T2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
240
0.300
0.598
1.593
100
240
0.536
0.566
0.843
150
240
0.776
0.546
0.559
Table 8.17
Frequency converter, P1K5, T4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
400
0.640
0.690
0.862
50
400
0.470
0.985
0.985
150
400
0.760
1.045
0.947
Table 8.18
General Specifications and ...
VLT
®
Refrigeration Drive Design Guide
MG16G102 - VLT
®
is a registered Danfoss trademark
119