6.
3-03 Maximum Reference
. Set maximum internal
frequency converter reference to 60 Hz. (This sets
the maximum frequency converter speed at 60
Hz. Note that 50/60 Hz is a regional variation.)
Q3-21
130B
T763.11
3-03 Maximum Reference
50.000 Hz
14.7% 0.00A 1(1)
Analog Reference
Illustration 5.5
7.
6-10 Terminal 53 Low Voltage
. Set minimum
external voltage reference on Terminal 53 at 0 V.
(This sets the minimum input signal at 0 V.)
Q3-21
130B
T764.10
6-10 Terminal 53 Low
Voltage
0.00 V
14.7% 0.00A 1(1)
Analog Reference
Illustration 5.6
8.
6-11 Terminal 53 High Voltage
. Set maximum
external voltage reference on Terminal 53 at 10 V.
(This sets the maximum input signal at 10 V.)
Q3-21
130B
T765.10
6-11 Terminal 53 High
Voltage
10.00 V
14.7% 0.00A 1(1)
Analog Reference
Illustration 5.7
9.
6-14 Terminal 53 Low Ref./Feedb. Value
. Set
minimum speed reference on Terminal 53 at 20
Hz. (This tells the frequency converter that the
minimum voltage received on Terminal 53 (0 V)
equals 20 Hz output.)
130B
T773.11
Q3-21
14.7 % 0.00 A 1(1)
Analog Reference
6 - 14 Terminal 53 Low
Ref./Feedb. Value
000020.000
Illustration 5.8
10.
6-15 Terminal 53 High Ref./Feedb. Value
. Set
maximum speed reference on Terminal 53 at 50
Hz. (This tells the frequency converter that the
maximum voltage received on Terminal 53 (10 V)
equals 50 Hz output.)
130B
T774.11
Q3-21
14.7 % 0.00 A 1(1)
Analog Reference
6 - 15 Terminal 53 High
Ref./Feedb. Value
50.000
Illustration 5.9
With an external device providing a 0-10 V control signal
connected to frequency converter terminal 53, the system
is now ready for operation. Note that the scroll bar on the
right in the last illustration of the display is at the bottom,
indicating the procedure is complete.
shows the wiring connections used to
enable this set up.
53
55
6-1*
+
A53
U - I
130BB482.10
0-10V
Illustration 5.10 Wiring Example for External Device Providing
0-10 V Control Signal
Programming
VLT
®
HVAC Drive D-Frame
Operating Instructions
28
MG16D102 - VLT
®
is a registered Danfoss trademark
5
5
Содержание VLT HVAC FC 100
Страница 1: ...MAKING MODERN LIVING POSSIBLE Operating Instructions D Frame VLT HVAC Drive FC 100...
Страница 3: ...Safety VLT HVAC Drive D Frame Operating Instructions MG16D102 VLT is a registered Danfoss trademark...
Страница 72: ...www danfoss com drives MG16D102 130R0290 MG16D102 Rev 2012 04 24...
Страница 73: ......