6.2 Electrical Data and Wire Sizes
Mains Supply 3x380-480 V AC
Frequency Converter
PK37
PK55
PK75
P1K1
P1K5
P2K2
P3K0
Rated Shaft Output [kW]
0.37
0.55
0.75
1.1
1.5
2.2
3.0
Rated Shaft Output [hp]
0.5
0.75
1.0
1.5
2.0
3.0
4.0
Max. input current
ON
WARNING
ALARM
Bus MS
NS2
NS1
130BB800.10
Continuous (3x380-440 V) [A]
1.2
1.6
2.2
2.7
3.7
5.0
6.5
Intermittent (3x380-440 V) [A]
1.9
2.6
3.5
4.3
5.9
8.0
10.4
Continuous (3x441-480 V) [A]
1.0
1.4
1.9
2.7
3.1
4.3
5.7
Intermittent (3x441-480 V) [A]
1.6
2.2
3.0
4.3
5.0
6.9
9.1
Recommended max. fuse size*
gG-25
Built-in circuit breaker (large unit)
CTI-25M Danfoss part no.: 047B3151
Recommended circuit breaker (small
unit)
CTI-45MB Danfoss part no.: 047B3164
Power loss at max. load [W]
35
42
46
58
62
88
116
Efficiency
0.93
0.95
0.96
0.96
0.97
0.97
0.97
Weight, small unit [kg]
9.8
N/A
Weight, large unit [kg]
13.9
Output current
ON
WARNING
ALARM
Bus MS
NS2
NS1
130BB799.10
Continuous (3x380-440 V) [A]
1.3
1.8
2.4
3.0
4.1
5.2
7.2
Intermittent (3x380-440 V) [A]
2.1
2.9
3.8
4.8
6.6
8.3
11.5
Continuous (3x441-480 V) [A]
1.2
1.6
2.1
3.0
3.4
4.8
6.3
Intermittent (3x441-480 V) [A]
1.9
2.6
3.4
4.8
5.4
7.7
10.1
Continuous kVA (400 V AC) [kVA]
0.9
1.3
1.7
2.1
2.8
3.9
5.0
Continuous kVA (460 V AC) [kVA]
0.9
1.3
1.7
2.4
2.7
3.8
5.0
Max. cable size: (mains, motor,
brake) [mm
2
/ AWG]
solid cable 6/10
flexible cable 4/12
Table 6.2 FCD 302 Shaft Output, Output Current and Input Current
*To meet UL/cULrequirements, use the following pre-fuses.
1.
American Wire Gauge. Max. Cable cross section is
the largest cable cross section that can be
attached to the terminals. Always observe
national and local regulations.
2.
Type gG pre-fuses must be used. To maintain UL/
cUL, use pre-fuses of these type (see
3.
Measured using a 10 m screened/armoured
motor cable with a rated load and rated
frequency.
Recommended maximum pre-fuse size 25 A
Brand
Fuse Type
UL File no.
UL Category
(CCN code)
Bussmann
FWH-25
E91958
JFHR2
Bussmann
KTS-R25
E52273
RK1/JDDZ
Bussmann
JKS-25
E4273
J/JDDZ
Bussmann
JJS-25
E4273
T/JDDZ
Bussmann
FNW-R-25
E4273
CC/JDDZ
Bussmann
KTK-R-25
E4273
CC/JDDZ
Bussmann
LP-CC-25
E4273
CC/JDDZ
SIBA
5017906-025 E180276
RK1/JDDZ
LITTLE FUSE
KLS-R25
E81895
RK1/JDDZ
FERRAZ-
SHAWMUT
ATM-R25
E163267/
E2137
CC/JDDZ
FERRAZ-
SHAWMUT
A6K-25R
E163267/
E2137
RK1/JDDZ
FERRAZ-
SHAWMUT
HSJ25
E2137
J/HSJ
Table 6.3 FCD 302 Pre-fuses Meeting UL/cUL Requirements
Specifications
VLT
®
Decentral Drive FCD 302
82
MG04H102 - VLT
®
is a registered Danfoss trademark
6
6