2.4.1 Earth Leakage Current
Follow national and local codes regarding protective
earthing of equipment with a leakage current >3.5 mA.
Frequency converter technology implies high frequency
switching at high power. This will generate a leakage
current in the earth connection. A fault current in the
frequency converter at the output power terminals might
contain a DC component which can charge the filter
capacitors and cause a transient earth current.
The earth leakage current is made up of several contri-
butions and depends on various system configurations
including RFI filtering, screened motor cables, and
frequency converter power.
a
b
130BB955.10
Cable length [m]
Leakage current [mA]
Illustration 2.20 Influence of Cable Length and Power Size on
Leakage Current for Pa>Pb
The leakage current also depends on the line distortion
130BB956.10
Leakage current [mA]
THVD=0%
THVD=5%
Illustration 2.21 Influence of Line Distortion on Leakage Current
NOTE
When a filter is used, turn off
14-50 RFI Filter
when
charging the filter, to avoid that a high leakage current
makes the RCD switch.
EN/IEC61800-5-1 (Power Drive System Product Standard)
requires special care if the leakage current exceeds 3.5 mA.
Earth grounding must be reinforced in one of the
following ways:
•
Earth ground wire (terminal 95) of at least 10
mm
2
•
Two separate earth ground wires both complying
with the dimensioning rules
See EN/IEC61800-5-1 and EN50178 for further information.
Using RCDs
Where residual current devices (RCDs), also known as earth
leakage circuit breakers (ELCBs), are used, comply with the
following:
•
Use RCDs of type B only which are capable of
detecting AC and DC currents
•
Use RCDs with an inrush delay to prevent faults
due to transient earth currents
•
Dimension RCDs according to the system configu-
ration and environmental considerations
L
leakage
[mA]
f [Hz]
f
sw
Cable
f
s
150 Hz
3rd harmonics
50 Hz
Mains
130BB958.10
RCD with low f
cut-off
RCD with high f
cut-off
Illustration 2.22 Main Contributions to Leakage Current
Leakage current [mA]
100 Hz
130BB957.10
2 kHz
100 kHz
Illustration 2.23 Influence of Cut-off Frequency of the RCD
See also
RCD Application Note, MN90G
.
2.5 Galvanic Isolation (PELV)
2.5.1 PELV - Protective Extra Low Voltage
PELV offers protection by way of extra low voltage.
Protection against electric shock is ensured when the
electrical supply is of the PELV type and the installation is
made as described in local/national regulations on PELV
supplies.
Product Overview
VLT
®
Decentral Drive FCD 302
24
MG04H102 - VLT
®
is a registered Danfoss trademark
2
2