NOTE
A warning of low voltage will be given when 24 V DC has
been connected; however, there will be no tripping.
WARNING
Use 24 V DC supply of type PELV to ensure correct
galvanic isolation (type PELV) on the control terminals of
the frequency converter.
3.4.1.2 DIP Switches
•
Analog input terminals 53 and 54 can select for
either voltage (0-10 V) or current (0-20 mA) input
signals
•
Set switches S201 (terminal 53) and S202
(terminal 54) to select the signal type. ON is for
current, OFF for voltage
•
Terminal 53 default is for a speed reference in
open loop
•
Terminal 54 default is for a feedback signal in
closed loop
130BB708.10
1
2
4
3
5
Illustration 3.12 Location of DIP Switches
1
S201 - terminal 53
2
S202 - terminal 54
3
S801 - standard bus termination
4
Profibus termination
5
Fieldbus address
Table 3.9 Legend
NOTE
Switches 4 and 5 are only valid for units fitted with
fieldbus options.
3.4.1.3 Basic Wiring Example
Connect terminals 27 and 37 to +24 V terminals 12 and 13,
as shown in
.
Default settings:
27=Coast inverse
5-10 Terminal 18 Digital Input
[2]
37=Safe torque off inverse
Speed
Coast inverse (27)
Coast inverse
Safe
torque off
130BC985.10
N
V
R
B03
B04
P
B02
B01
20
12
G
B07
B08
20
B06
B05
37
20
13
B11
B12
37
B10
B09
12
12
12
12
12
12
55
53
27
19
18
33
32
29
50
54
20
20
20
20
20
20
55
42
Illustration 3.13 Basic Wiring Example
3.4.1.4 Electrical Installation, Control Cables
System Integration
VLT
®
Decentral Drive FCD 302
36
MG04H102 - VLT
®
is a registered Danfoss trademark
3
3