Conn.
Term.
Input/Output
Type
Function
X55
1
Input
Normally open, dry relay contact Closed when motor can start to
run
2
Input
3
Input
Normally open, dry relay contact Closed for remote start with
common start/stop
4
Input
5
Input
Normally open, dry relay contact Safety input, open to stop
6
Input
7
Input
Normally open, dry relay contact Closed to enable Fire Mode
8
Input
9
Output
Normally open, dry relay contact Closed indicates Fire Mode
activated
10
Output
11
Output
Normally open, dry relay contact Closed indicates Motor 1 selected
12
Output
Conn.
Term.
Input/Output
Type
Function
X56
1
Output
Normally open, dry relay contact Closed indicates Motor 2 selected
2
Output
3
Output
Normally open, dry relay contact Closed when panel is in Drive
Mode
4
Output
5
Output
Normally open, dry relay contact Closed when panel is in Bypass
Mode
6
Output
7
Output
Normally open, dry relay contact Open when drive is in Fault
Condition
8
Output
Common form C relay contact
Common for fault relay
9
Output
Normally closed form C relay
contact
Closed when drive is in Fault
Condition
10
Input
Normally open, dry relay contact CMS Motor 2, close to select
11
Input
Normally open, dry relay contact CMS common
12
Input
Normally open, dry relay contact CMS Motor 1, close to select
Conn.
Term.
Input/Output
Type
Function
X58
1
Output
Normally open, dry relay contact Closed indicates run requested
2
Output
Table 5.1 EMB2 Control Card Terminal Functions
130BX226.10
1
2
3
4
Illustration 5.2 EMB2 Control Card
1 Switch S103 autobypass timer
2 Terminal X56
3 Terminal X55
4 Terminal X58
Table 5.2 Legend to
Illustration 5.2
Electromechanical Bypass (E...
Option Panel Operating Instructions
34
MG14I102 - VLT
®
is a registered Danfoss trademark
5