11 Specifications
11.1 Power-dependent Specifications
N110
N132
N160
N200
N250
N315
P355
P400
P450
Normal Load*
NO
NO
NO
NO
NO
NO
NO
NO
NO
Typical Shaft output at 400 V [kW]
110
132
160
200
250
315
355
400
450
Typical Shaft output at 460 V [hp]
150
200
250
300
350
450
500
550
600
Enclosure IP21
D1h
D1h
D1h
D2h
D2h
D2h
E1
E1
E1
Enclosure IP54
D1h
D1h
D1h
D2h
D2h
D2h
E1
E1
E1
Enclosure IP20
D3h
D3h
D3h
D4h
D4h
D4h
-
-
-
Enclosure IP00
-
-
-
-
-
-
E2
E2
E2
Output current
Continuous (at 400 V) [A]
212
260
315
395
480
588
658
745
800
Intermittent (60 s overload) (at 400 V)[A]
233
286
347
435
528
647
724
820
880
Continuous (at 460/480 V) [A]
190
240
302
361
443
535
590
678
730
Intermittent (60 s overload) (at 460/480 V)
[kVA]
209
264
332
397
487
588
649
746
803
Continuous kVA (at 400 V) [kVA]
147
180
218
274
333
407
456
516
554
Continuous kVA (at 460 V) [kVA]
151
191
241
288
353
426
470
540
582
Max. Input current
Continuous (at 400 V) [A]
204
251
304
381
463
567
647
733
787
Continuous (at 460/480 V) [A]
183
231
291
348
427
516
580
667
718
Max. external mains fuses [A]
315
350
400
550
630
800
900
Max. cable size
Max. cable size: mains, motor and load
share mm (AWG)]
2 x95 (2x3/0)
2x185 (2x350)
4x240 (4x500 mcm)
Max. cable size: brake mm (AWG)]
2 x95 (2x3/0)
2x185 (2x350)
2x185 (2x350 mcm)
Estimated power loss at 400 V [W]
2555
2949
3764
4109
5129
6663
7532
8677
9473
Estimated power loss at 460 V [W]
2257
2719
3612
3561
4558
5703
6724
7819
8527
Weight, enclosure IP21, IP54 kg (lbs.)
62 (135)
125 (275)
270
(594)
272
(598)
277
(609)
Weight, enclosure IP20 kg (lbs.)
62 (135)
125 (275)
-
-
-
Weight, enclosure IP00 kg (lbs)
-
234
(515)
236
(519)
313
(689)
Efficiency
0.98
Output frequency [Hz]
0-590 Hz
Heat sink overtemp. trip [
°
C]
110
Power card ambient trip [
°
C]
75
85
*Normal overload=110% current for 60 s
Table 11.1 Mains Supply 3x380-480 V AC
Specifications
Operating Instructions
MG16J202
Danfoss A/S © Rev. 05/2014 All rights reserved.
95
11
11
Содержание VLT FC 103