4.3.2 Required Initial Frequency Converter
Programming
NOTICE
If the wizard is run, ignore the following.
Frequency converters require basic operational
programming before running for best performance. This
requires entering motor-nameplate data for the motor
being operated and the minimum and maximum motor
speeds. Enter data in accordance with the following
procedure. Parameter settings recommended are intended
for start-up and checkout purposes. Application settings
may vary. See
for detailed
instructions on entering data via the LCP.
Enter data with power ON, but before operating the
frequency converter.
1.
Press [Main Menu] twice on the LCP.
2.
Press the navigation keys to scroll to parameter
group
0-** Operation/Display
and press [OK].
130BP066.10
1107 RPM
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
3.84 A
1 (1)
Main menu
Illustration 4.26 Main Menu
3.
Press the navigation keys to scroll to parameter
group
0-0* Basic Settings
and press [OK].
0-
**
Operation / Display
0.0%
0-0
*
Basic Settings
0-1
*
Set-up Operations
0-2
*
LCP Display
0-3
*
LCP Custom Readout
0.00A
1(1)
130BP087.10
Illustration 4.27 Operation/Display
4.
Press the navigation keys to scroll to
0-03 Regional Settings
and press [OK].
0-0
*
Basic Settings
0.0%
0-03 Regional Settings
[0] International
0.00A
1(1)
130BP088.10
Illustration 4.28 Basic Settings
5.
Press the navigation keys to select
[0] Interna-
tional
or
[1] North America
as appropriate and
press [OK]. (This changes the default settings for
a number of basic parameters. See
chapter 6.4 International/North American Default
Parameter Settings
for a complete list.)
6.
Press [Quick Menu] on the LCP.
7.
Press the navigation keys to scroll to parameter
group
Q2 Quick Setup
and press [OK].
130BB847.10
Q1 My Personal Menu
Q2 Quick Setup
Q5 Changes Made
Q6 Loggings
13.7% 13.0A 1(1)
Quick Menus
Illustration 4.29 Quick Menus
8.
Select the language and press [OK].
9.
A jumper wire should be in place between
control terminals 12 and 27. If this is the case,
leave
5-12 Terminal 27 Digital Input
at factory
default. Otherwise select
No Operation
. For
frequency converters with an optional Danfoss
bypass, no jumper wire is required.
10.
Set
3-02 Minimum Reference
11.
Set
3-03 Maximum Reference
12.
Set
3-41 Ramp 1 Ramp Up Time
13.
Set
3-42 Ramp 1 Ramp Down Time
14.
Set
3-13 Reference Site
. Linked to Hand/Auto*
Local Remote.
Start-up and Functional Tes...
Operating Instructions
60
Danfoss A/S © Rev. 05/2014 All rights reserved.
MG16J202