9.4 Warning and Alarm Definitions
defines whether a warning is issued before an alarm, and whether the alarm trips the unit or trip locks the unit.
No.
Description
Warning
Alarm/Trip
Alarm/Trip lock
Parameter reference
1
10 Volts low
X
2
Live zero error
(X)
(X)
6-01 Live Zero Timeout
Function
4
Mains phase loss
(X)
(X)
(X)
14-12 Function at Mains
Imbalance
5
DC link voltage high
X
6
DC link voltage low
X
7
DC over voltage
X
X
8
DC under voltage
X
X
9
Inverter overloaded
X
X
10
Motor ETR over temperature
(X)
(X)
1-90 Motor Thermal Protection
11
Motor thermistor over temperature
(X)
(X)
1-90 Motor Thermal Protection
12
Torque limit
X
X
13
Over Current
X
X
X
14
Earth (ground) fault
X
X
X
15
Hardware mismatch
X
X
16
Short Circuit
X
X
17
Control word timeout
(X)
(X)
8-04 Control Timeout Function
18
Start Failed
X
1-77 Compressor Start Max
Speed [RPM]
,
1-79 Pump Start Max Time to
Trip
19
Discharge Temperature High
X
28-25 Warning Action
28-26 Emergency Level
23
Internal Fan Fault
X
24
External Fan Fault
X
14-53 Fan Monitor
29
Drive over temperature
X
X
X
30
Motor phase U missing
(X)
(X)
(X)
4-58 Missing Motor Phase
Function
31
Motor phase V missing
(X)
(X)
(X)
4-58 Missing Motor Phase
Function
32
Motor phase W missing
(X)
(X)
(X)
4-58 Missing Motor Phase
Function
33
Inrush fault
X
X
34
Fieldbus communication fault
X
X
35
Out of frequency range
X
X
36
Mains failure
X
X
38
Internal fault
X
X
39
Heatsink sensor
X
X
40
Overload of Digital Output Terminal 27
(X)
5-00 Digital I/O Mode,
5-01 Terminal 27 Mode
41
Overload of Digital Output Terminal 29
(X)
5-00 Digital I/O Mode,
5-02 Terminal 29 Mode
42
Overload of Digital Output On X30/6
(X)
5-32 Term X30/6 Digi Out (MCB
101)
42
Overload of Digital Output On X30/7
(X)
5-33 Term X30/7 Digi Out (MCB
101)
46
Pwr. card supply
X
X
47
24 V supply low
X
X
X
48
1.8 V supply low
X
X
Warnings and Alarms
Operating Instructions
84
Danfoss A/S © Rev. 05/2014 All rights reserved.
MG16J202