![Danfoss VLT Ea4 Скачать руководство пользователя страница 73](http://html1.mh-extra.com/html/danfoss/vlt-ea4/vlt-ea4_operating-manual_3870291073.webp)
All control characteristics are based on a 4-pole asynchronous motor.
7.7.12 Control Card Performance
Scan interval
5 ms
7.7.13 Control Card, USB Serial Communication
USB standard
1.1 (full speed)
(1)
USB plug
USB type B plug
(2)(3)
1
Connection to PC is carried out via a standard host/device USB cable.
2
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
3
The USB connection is not galvanically isolated from ground. Use only isolated laptop/PC as connection to the USB connector on the drive or an
isolated USB cable/converter.
7.8 Fuses
Fuses installed on the supply side ensure that if a component breakdown (first fault) occurs inside the drive, any potential damage is
contained within the drive enclosure. For a list of fuses, see
. The drive modules are supplied with built-in AC fuses.
Table 23: Fuse Options
Input voltage [V]
Type of fuse
Bussmann part number
380–500
AC fuse
170M7309
DC fuse
170M5468
AQ434333248451en-000101 / 130R1286 | 73
Danfoss A/S © 2023.01
Specifications
VLT Ea4 Parallel Drive Modules
Operating Guide
Содержание VLT Ea4
Страница 1: ...Operating Guide VLT Ea4 Parallel Drive Modules...
Страница 2: ......
Страница 74: ......