Connect the 3-phase motor wiring to terminals 96 (U), 97 (V), and 98 (W).
Tighten the terminals fasteners. See
5.9 Connecting to the AC Mains
Comply with local and national electrical codes for cable sizes. See
7.1 Electrical Data, 380–500 V AC
N O T I C E
SUPPLY SIDE FUSES
Fuses installed on the supply side ensure that if a component breakdown (first fault) occurs inside the drive module, any potential
damage is contained inside the drive enclosure. Each drive module is provided with fast-acting semiconductor fuses on the sup-
ply side for protection of the drive module.
N O T I C E
MULTIPLE MAINS CABLES
If connecting more than 1 set of mains terminals, use the same number, size, and length of cables for each set of terminals. For
example, do not use 1 cable on one mains terminal and 2 cables on another mains terminal.
Procedure
Strip a section of the outer cable insulation.
Establish mechanical fixation and electrical contact between the cable shield and ground by positioning the stripped wire
under the cable clamp.
Connect the 3-phase AC input power wiring to terminals R, S, and T.
Tighten the terminals fasteners. See
When supplied from an isolated mains source (IT mains or floating delta) or TT/TN-S mains with a grounded leg (grounded
delta), ensure that
parameter 14-50 RFI Filter
is set to
[0] Off
to avoid damage to the DC link and to reduce ground capacity
currents.
AQ434333248451en-000101 / 130R1286
28 | Danfoss A/S © 2023.01
Electrical Installation
VLT Ea4 Parallel Drive Modules
Operating Guide