Operation
status
Description
[14] Jog
was selected as function for a digital input (
parameter group 5–1* Digital Inputs
). The corresponding
terminal (for example, terminal 29) is active.
The jog function is activated via the serial communication.
The jog function was selected as a reaction for a monitoring function (for example, No signal). The monitoring
function is active.
OVC control
Overvoltage control was activated by
[2] Enabled
in
parameter 2-17 Over-voltage Control
. The connected motor is
supplying the drive with generative energy. The overvoltage control adjusts the V/Hz ratio to run the motor in
controlled mode and to prevent the drive from tripping.
Power unit
off
(For drives with a 24 V external supply installed only.) Mains supply to the drive is removed, but the control card is
supplied by the external 24 V.
Protection
md
Protection mode is active. The unit has detected a critical status (an overcurrent or overvoltage).
To avoid tripping, the switching frequency is reduced to 1.5 kHz if
parameter 14-55 Output Filter
is set to
[2]
Sine-Wave Filter Fixed
. Otherwise, the switching frequency is reduced to 1.0 kHz.
If possible, protection mode ends after approximately 10 s.
Protection mode can be restricted in
parameter 14-26 Trip Delay at Inverter Fault
.
Qstop
The motor is decelerating using
parameter 3-81 Quick Stop Ramp Time
.
[4] Quick stop inverse
was selected as a function for a digital input (
parameter group 5–1* Digital Inputs
). The
corresponding terminal is not active.
The quick stop function was activated via serial communication.
Ramping
The motor is accelerating/decelerating using the active ramp up/down. The reference, a limit value, or a standstill
is not yet reached.
Ref. high
The sum of all active references is above the reference limit set in
parameter 4-55 Warning Reference High
.
Ref. low
The sum of all active references is below the reference limit set in
parameter 4-54 Warning Reference Low
.
Run on ref.
The drive is running in the reference range. The feedback value matches the setpoint value.
Run request
A start command has been given, but the motor is stopped until a run permissive signal is received via digital
input.
Running
The drive is driving the motor.
Sleep mode
The energy-saving function is enabled. This function being enabled means that now the motor has stopped, but
that it restarts automatically when required.
Speed high
The motor speed is above the value set in
parameter 4-53 Warning Speed High
.
Speed low
The motor speed is below the value set in
parameter 4-52 Warning Speed Low
.
Standby
In auto-on mode, the drive starts the motor with a start signal from a digital input or serial communication.
Start delay
In
parameter 1-71 Start Delay
, a delay starting time was set. A start command is activated and the motor starts after
the start delay time expires.
Start
fwd/rev
[12] Enable Start Forward
and
[13] Enable Start Reverse
were selected as functions for 2 different digital inputs
(
parameter group 5–1* Digital Inputs
). The motor starts in forward or reverse depending on which corresponding
terminal is activated.
Stop
The drive has received a stop command from 1 of the following:
AQ434333248451en-000101 / 130R1286 | 45
Danfoss A/S © 2023.01
Operating the Drive
VLT Ea4 Parallel Drive Modules
Operating Guide