![Danfoss VLT Ea4 Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/danfoss/vlt-ea4/vlt-ea4_operating-manual_3870291029.webp)
5.10 Example of the Ground, Motor, and Mains Wiring
e3
0b
k4
49
.1
0
L1, L2, L3
U/T1, V/T2, W/T3
M10 [19 Nm (168 in-lb)]
M8 [9.6 Nm (84 in-lb)]
M10 [19 Nm (168 in-lb)]
L1, L2, L3
U/T1, V/T2, W/T3
-DC, R-, +DC, R+
M10 [19 Nm (168 in-lb)]
M12 [35 Nm (310 in-lb)]
M10 [19 Nm (168 in-lb)]
M12 [35 Nm (310 in-lb)]
17 mm
Illustration 13: Ground, Motor, Mains Wiring Example
5.11 Installing Control Wiring
5.11.1 Control Terminals
12 13 18 19 27 29 32 33 20 37
39
69
68
61
42 50 53 54 55
e3
0b
f1
45
.1
1
1
2
4
3
Illustration 14: Control Terminal Locations
1
Terminals (+) 68 and (-) 69 are for serial communica-
tion connection.
2
USB port available for use with the MCT 10 setup
software.
3
4 programmable digital input terminals, 2 extra digi-
tal terminals programmable as either input or out-
put, a 24 V DC supply voltage, and a common for
optional customer-supplied 24 V DC voltage.
4
2 analog inputs, 1 analog output, 10 V DC supply
voltage, and commons for the inputs and output.
AQ434333248451en-000101 / 130R1286 | 29
Danfoss A/S © 2023.01
Electrical Installation
VLT Ea4 Parallel Drive Modules