Enclosure
type
Power
1)
[kW]
3x
380-480
V
Circuit Breaker
Fuse
Rec. UL
Max. UL
Rec.
non-
UL
Max.
non-
UL
Rec.
UL
Maximum UL
Rec.
non-UL
Max.
non-UL
Type
RK5,
RK1,
J, T,
CC
RK5 RK1
J
T
CC
gG
gG
MH1
0.55
CTI25M -
047B3146
CTI25M -
047B3149
CTI25
M -
047B3
146
CTI25
M -
047B3
149
6
6
6
6
6
6
10
10
0.75
CTI25M -
047B3147
CTI25M -
047B3149
CTI25
M -
047B3
147
CTI25
M -
047B3
149
6
6
6
6
6
6
10
10
1.1
CTI25M -
047B3147
CTI25M -
047B3150
CTI25
M -
047B3
147
CTI25
M -
047B3
150
6
10
10
10
10
10
10
10
1.5
CTI25M -
047B3148
CTI25M -
047B3150
CTI25
M -
047B3
148
CTI25
M -
047B3
150
6
10
10
10
10
10
10
10
MH2
2.2
CTI25M -
047B3149
CTI25M -
047B3152
CTI25
M -
047B3
149
CTI25
M -
047B3
152
6
20
20
20
20
20
16
20
3.0
CTI25M -
047B3149
CTI25M -
047B3152
CTI25
M -
047B3
149
CTI25
M -
047B3
152
15
25
25
25
25
25
16
25
4.0
CTI25M -
047B3150
CTI25M -
047B3102
CTI25
M -
047B3
150
CTI25
M -
047B3
102
15
30
30
30
30
30
16
32
MH3
5.5
CTI25M -
047B3150
CTI25M -
047B3102
CTI25
M -
047B3
150
CTI25
M -
047B3
102
20
30
30
30
30
30
25
32
7.5
CTI25M -
047B3151
CTI25M -
047B3102
CTI25
M -
047B3
151
CTI25
M -
047B3
102
25
30
30
30
30
30
25
32
Table 6.13 Fuses and Circuit Breakers
1) Power ratings relate to NO, see chapter 6.2 Electrical Data.
Specifications
VLT
®
DriveMotor FCP 106 and FCM 106 Design Guide
MG03M102 -
08/2015
59
6
6