3.5.6 Mains and Motor Connection with Service Switch
3.5.7 Connection of HAN 10E Motor Plug for T73
HAN 10E pin no 1 - Motor phase U
HAN 10E pin no 2 - Motor phase V
HAN 10E pin no 3 - Motor phase W
HAN 10E pin no 4 - Motor brake, see
Operating Instructions MG.
04.BX.YY
, terminal 122
HAN 10E pin no 5 - Motor brake, see
Operating Instructions MG.
04.BX.YY
, terminal 123
HAN 10E pin no 9 - Motor thermistor, see
Operating Instructions
MG.04.BX.YY
, terminal 31A
HAN 10E pin no 10 - Motor thermistor, see
Operating Instruc-
tions MG.04.BX.YY
, terminal 31B
PE = protective earth
3.5.8 Parallel Connection of Motors
The frequency converter is able to control several motors connected in
parallel. If the motors are to have different rpm values, use motors with
different rated rpm values. Motor rpm is changed simultaneously, which
means that the ratio between the rated rpm values is maintained across
the range. The total current consumption of the motors is not to exceed
the maximum rated output current I
INV
for the frequency converter.
VLT
®
Decentral FCD 300 Design Guide
3 Installation
MG.90.S1.02 - VLT
®
is a registered Danfoss trademark