Function:
See function description for parameter 502
Coasting stop.
Description of choice:
The table below shows when the motor is running clockwise and anti-
clockwise when each of the following is selected:
Digital input
[0],
Serial
port
[1],
Logic and
[2] or
Logic or
[3].
Digital input
[0]
Dig. input
Ser. port
Function
0
0
Clockwise
0
1
Clockwise
1
0
Anti-clockwise
1
1
Anti-clockwise
Serial port
[1]
Dig. input
Ser. port
Function
0
0
Clockwise
0
1
Anti-clockwise
1
0
Clockwise
1
1
Anti-clockwise
Logic and
[2]
Dig. input
Ser. port
Function
0
0
Clockwise
0
1
Clockwise
1
0
Clockwise
1
1
Anti-clockwise
Logic or
[3]
Dig. input
Ser. port
Function
0
0
Clockwise
0
1
Anti-clockwise
1
0
Anti-clockwise
1
1
Anti-clockwise
507
Selection of Setup
Value:
Digital input (DIGITAL INPUT)
[0]
Serial communication (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
Logic or (LOGIC OR)
[3]
Function:
See function description of parameter 502
Coasting stop.
Description of choice:
The table below shows which Setup (parameter 004
Active Setup
) is
selected for each of the following:
Digital input
[0],
Serial communica-
tion
[1],
Logic and
[2] or
Logic or
[3].
Digital input
[0]
Setup msb
Setup lsb
Function
0
0
Setup 1
0
1
Setup 2
1
0
Setup 3
1
1
Setup 4
Serial communication
[1]
Setup msb
Setup lsb
Function
0
0
Setup 1
0
1
Setup 2
1
0
Setup 3
1
1
Setup 4
Logic and
[2]
Bus Setup
msb
Bus Setup
lsb
Dig. Setup
msb
Dig. Setup
lsb
Setup no.
0
0
0
0
1
0
0
0
1
1
0
0
1
0
1
0
0
1
1
1
0
1
0
0
1
0
1
0
1
2
0
1
1
0
1
0
1
1
1
2
1
0
0
0
1
1
0
0
1
1
1
0
1
0
3
1
0
1
1
3
1
1
0
0
1
1
1
0
1
2
1
1
1
0
3
1
1
1
1
4
Logic or
[3]
Bus Setup
msb
Bus Setup
lsb
Dig. Setup
msb
Dig. Setup
lsb
Setup no.
0
0
0
0
1
0
0
0
1
2
0
0
1
0
3
0
0
1
1
4
0
1
0
0
2
0
1
0
1
2
0
1
1
0
4
0
1
1
1
4
1
0
0
0
3
1
0
0
1
4
1
0
1
0
3
1
0
1
1
4
1
1
0
0
4
1
1
0
1
4
1
1
1
0
4
1
1
1
1
4
508
Selection of preset ref.
Value:
Digital input (DIGITAL INPUT)
[0]
Serial comunication (SERIAL PORT)
[1]
Logic and (LOGIC AND)
[2]
Logic or (LOGIC OR)
[3]
Function:
See function description of parameter 502
Coasting stop.
Description of choice:
Preset references via serial communication are active when parameter
512
Telegram profile
is set to
FC protocol
[1].
509
Bus jog 1 (BUS JOG 1 FREQ.)
510
Bus jog 2 (BUS JOG 2 FREQ.)
Value:
0.0 - par. 202
Output frequency high limit
10,0 Hz
Function:
If parameter 512
Telegram Profile
shows the selection
Profidrive
[0], two
fixed speeds (Jog 1 or Jog 2) can be selected via the serial port.
The function is the same as in parameter 213
Jog frequency
.
Description of choice:
Jog frequency f
JOG
can be selected between 0 Hz and f
MAX
.
VLT
®
Decentral FCD 300 Design Guide
4 Programming
MG.90.S1.02 - VLT
®
is a registered Danfoss trademark
111
4