Input 37 Safe Stop
Option:
Function:
Terminal 37 must be closed for the frequency converter to run. If this input is opened while running
the frequency converter will coast to a stop.
Output O1 End of Roll Indicator
Option:
Function:
This output turns ON to indicate that the diameter has reached the value programmed in parameter
19-12. This output turns OFF when Diameter is reset (Input 8) to a value in normal operating range.
Output O2 TLD Indicator
Option:
Function:
This output is turned ON when the Tension Limit Detector has sensed that tension has been out of
range as set in parameters 19-08 and 19-09 for the number of scans set in parameter 19-10. A
Tension Limit results in a Winder fault. Turning the tension OFF resets this fault and the output.
Output O3 Running on Tension
Option:
Function:
This output is turned ON when the winder is regulating tension. The output is turned OFF when
tension is switched off or if there is a station fault. Turning the tension OFF resets this fault and the
output.
Output O4 Ready
Option:
Function:
This output is turned ON when the station is ready to run. The output turns OFF if there is a TLD
fault, an FC Alarm, an MCO 305 Error, Commanded Quick Stop, or Commanded Coast. Note: Outputs
5-8 are not used.
Relay 01 Running on Tension
Option:
Function:
This relay output (01, 02, 03) is energized when the winder is regulating tension. The relay output
is de-energized when tension is switched off or if there is a station fault.
NB!
Parameter 5-40 must be set for MCO controlled [51] for this function to work as described.
Relay 02 Ready
Option:
Function:
This relay output (04, 05, 06) is energized when the station is ready to run. The relay will de-energize
on a TLD fault, an FC Alarm, an MCO 305 Error, Quick Stop, or Coast.
VLT
®
Center Winder MCO 352
4 How to Install
MG.33.T1.02 - VLT
®
is a registered Danfoss trademark
15
4
Содержание VLT Center Winder MCO 352
Страница 10: ...4 How to Install VLT Center Winder MCO 352 10 MG 33 T1 02 VLT is a registered Danfoss trademark 4 ...
Страница 32: ...6 Troubleshooting VLT Center Winder MCO 352 32 MG 33 T1 02 VLT is a registered Danfoss trademark 6 ...
Страница 34: ...7 Appendix VLT Center Winder MCO 352 34 MG 33 T1 02 VLT is a registered Danfoss trademark 7 ...