Relay output
Programmable relay output
2
Relay 01 and 02
01-03 (NC), 01-02 (NO), 04-06 (NC), 04-05 (NO)
Maximum terminal load (AC-1)
1)
on 01-02/04-05 (NO) (Resistive load)
250 V AC, 3 A
Maximum terminal load (AC-15)
1)
on 01-02/04-05 (NO) (Inductive load @ cos
φ
0.4)
250 V AC, 0.2 A
Maximum terminal load (DC-1)
1)
on 01-02/04-05 (NO) (Resistive load)
30 V DC, 2 A
Maximum terminal load (DC-13)
1)
on 01-02/04-05 (NO) (Inductive load)
24 V DC, 0.1 A
Maximum terminal load (AC-1)
1)
on 01-03/04-06 (NC) (Resistive load)
250 V AC, 3 A
Maximum terminal load (AC-15)
1)
on 01-03/04-06 (NC) (Inductive load @ cos
φ
0.4)
250 V AC, 0.2 A
Maximum terminal load (DC-1)
1)
on
01-03/04-06 (NC) (Resistive load)
30 V DC, 2 A
Minimum terminal load on 01-03 (NC), 01-02 (NO) 24 V DC 10 mA, 24 V AC 20
mA
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
1) IEC 60947 parts 4 and 5.
Control card, 10 V DC output
1)
Terminal number
50
Output voltage
10.5 V
±
0.5 V
Maximum load
25 mA
1) All inputs, outputs, circuits, DC supplies and relay contacts are galvanically isolated from the supply voltage (PELV) and other
high-voltage terminals.
Surroundings
Enclosure
IP20
Enclosure kit available.
IP21, TYPE 1
Vibration test
1.0 g
Maximum relative humidity
5%–95% (IEC 60721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60721-3-3), coated (standard)
Class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
122°F [50
°
C]
Derating for high ambient temperature, see
chapter 1.8 Special Conditions
.
Minimum ambient temperature during full-scale operation
32°F [0
°
C]
Minimum ambient temperature at reduced performance
-4°F [-20
°
C]
Temperature during storage/transport
-22°–149°/158°F [-30°–+65/70
°
C]
Maximum altitude above sea level without derating
3,300 ft [1000 m]
Maximum altitude above sea level with derating
10,000 ft [3000 m]
Derating for high altitude, see
chapter 1.8 Special Conditions
Safety standards
EN/IEC 61800-5-1, UL 508C
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards,
Immunity
EN 61800-3, EN 61000-3-12, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN
61000-4-5, EN 61000-4-6
Quick Guide
Quick Guide
30
Danfoss A/S © Rev. 08/2014 All rights reserved.
MG18M122
1
1