![Danfoss VLT CDS 803 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/danfoss/vlt-cds-803/vlt-cds-803_quick-manual_3757825023.webp)
Parameter
Option
Default
Function
8-01 Control Site
[0] Digital and ctrl.word
[1] Digital only
[2] Controlword only
[0] Digital and
ctrl.word
Select if digital, bus, or a combination of both
should control the adjustable frequency drive.
8-30 Protocol
[0] FC
[2] Modbus RTU
[0] FC
Select the protocol for the integrated RS-485
port.
8-32 Baud Rate
[0] 2,400 Baud
[1] 4,800 Baud
[2] 9,600 Baud
[3] 19,200 Baud
[4] 38,400 Baud
[5] 57,600 Baud
[6] 76,800 Baud
[7] 115,200 Baud
[2] 9,600 Baud
Select the baud rate for the RS-485 port.
20-00 Feedback 1 Source
[0] No function
[1] Analog Input 53
[2] Analog Input 54
[3] Pulse input 29
[100] Bus Feedback 1
[101] Bus Feedback 2
[0] No function
Select which input will be used as the source
of the feedback signal.
20-01 Feedback 1 Conversion
[0] Linear
[1] Square root
[0] Linear
Select how the feedback should be calculated
Table 1.15 Closed-loop Applications Set-up