The Start-up Wizard for compressor functions
28-13 Boost Duration
60 s
5
6
28-01 Interval between Starts
130BD874.11
28-11 Low Speed Running Time
20 min
28-02 Minimum Run Time
3
28-00 Short Cycle Protection
[1]
Enabled
1
28-10 Oil Return Management
[1]
On
4
2
300 s
60 s
Figure 1.16 Compressor Function Wizard
Compressor function wizard
Parameter
Option
Default
Function
28-00 Short Cycle Protection
[0] Disabled
[1] Enabled
[1] Enabled
Select if short cycle protection is to be used.
28-01 Interval between Starts
0–3600 s
300 s
Enter the minimum allowed time between
starts.
28-02 Minimum Run Time
10–3600 s
60 s
Enter the minimum allowed time to run
before stop.
28-10 Oil Return Management
[0] Off
[1] On
[1] On
Select if Oil Return Management is to be used.
28-11 Low Speed Running Time
1–1400 min
20 min
Enter the low speed running time.
28-13 Boost Duration
10–3600 s
60 s
Enter the boost duration for the oil return.
Table 1.14 Compressor Function