1.3.8 EMC-compatible Electrical Installation
General points to be observed to ensure EMC-compatible electrical installation.
•
Use only shielded/armored motor cables and shielded/armored control cables.
•
Connect the shield to ground at both ends.
•
Avoid installation with twisted shield ends (pigtails), since this ruins the shielding effect at high frequencies. Use
the cable clamps provided instead.
•
Ensure the same potential between adjustable frequency drive and ground potential of PLC.
•
Use starwashers and galvanically grounding plates.
L1
L2
L3
PE
Min. 0.0248 in
2
[16 mm
2
]
Equalizing cable
Control cables
All cable entries in
one side of panel
Grounding rail
Cable insula-
tion stripped
Output con-
tactor, etc.
Motor cable
Motor, 3 phases and
PLC etc.
Panel
Line power supply
Min. 7.9 in [200 mm]
between control
cable, line cable
and between line power
motor cable
PLC
Protective ground
Reinforced protective ground
130BB761.10
Figure 1.8 EMC-compatible Electrical Installation
For North America, use metal conduits instead of shielded cables.