13-10 Comparator Operand
Array [6]
Option:
Function:
Select the variable to be monitored by
the comparator.
[0]
DISABLED
The comparator is disabled.
[1]
Reference
The resulting remote reference (not local)
as a percentage.
[2]
Feedback
In the unit [RPM] or [Hz]
[3]
Motor speed
[RPM] or [Hz]
[4]
Motor Current
[A]
[5]
Motor torque
[Nm]
[6]
Motor power
[kW] or [hp]
[7]
Motor voltage
[V]
[8]
DC-link voltage [V]
[9]
Motor Thermal
Expressed as a percentage.
[10]
VLT temp.
Expressed as a percentage.
[11]
Heat sink temp. Expressed as a percentage.
[12]
Analog input
AI53
Expressed as a percentage.
[13]
Analog input
AI54
Expressed as a percentage.
[14]
Analog input
AIFB10
[V]. AIFB10 is internal 10 V supply.
[15]
Analog input
AIS24V
[V] Analog input AICCT [17] [°]. AIS24V is
switch mode power supply: SMPS 24V.
[17]
Analog input
AICCT
[°]. AICCT is control card temperature.
[18]
Pulse input
FI29
Expressed as a percentage.
[19]
Pulse input
FI33
Expressed as a percentage.
[20]
Alarm number
The error number.
[21]
Warning
number
[22]
Analog input
x30 11
[23]
Analog input
x30 12
[30]
Counter A
Number of counts
[31]
Counter B
Number of counts
[50]
FALSE
Enters the fixed value of false in the
comparator.
[51]
TRUE
Enters the fixed value of true in the
comparator.
[52]
Control ready
The control board receives supply voltage
13-10 Comparator Operand
Array [6]
Option:
Function:
[53]
Drive ready
The frequency converter is ready for
operation and applies a supply signal on
the control board.
[54]
Running
The motor is running.
[55]
Reversing
The output is high when the frequency
converter is running counter clockwise
(the logical product of the status bits
“running” AND “reverse”).
[56]
In range
The motor is running within the
programmed current and speed ranges
set in
parameter 4-50 Warning Current Low
to
parameter 4-53 Warning Speed High
[60]
On reference
The motor is running on reference.
[61]
Below
Reference Low
The motor is running below the value
given in
parameter 4-54 Warning Reference
Low
.
[62]
Above ref, high The motor is running above the value
given in
parameter 4-55 Warning Reference
High
[65]
Torque limit
The torque limit, set in
parameter 4-16 Torque Limit Motor Mode
or
parameter 4-17 Torque Limit Generator
Mode
, has been exceeded.
[66]
Current Limit
The motor current limit, set in
parameter 4-18 Current Limit
, has been
exceeded.
[67]
Out of current
range
The motor current is outside the range
set in
parameter 4-18 Current Limit
.
[68]
Below I low
The motor current is lower than set in
parameter 4-50 Warning Current Low
.
[69]
Above I high
The motor current is higher than set in
parameter 4-51 Warning Current High
.
[70]
Out of speed
range
The speed is outside the range set in
parameter 4-52 Warning Speed Low
and
parameter 4-53 Warning Speed High
.
[71]
Below speed
low
The output speed is lower than the
setting in
parameter 4-52 Warning Speed
Low
.
[72]
Above speed
high
The output speed is higher than the
setting in
[75]
Out of feedb.
range
The feedback is outside the range set in
parameter 4-56 Warning Feedback Low
and
parameter 4-57 Warning Feedback High
.
Parameter Descriptions
Operating Instructions
MG34M422
Danfoss A/S © Rev. 2013-07-03 All rights reserved.
89