6.13.4 16-6* Inputs and Outputs
16-60 Digital Input
Range:
Function:
0
*
[0 -
1023 ]
View the signal states from the active digital inputs.
Example: Input 18 corresponds to bit no. 5, ‘0’ = no
signal, ‘1’ = connected signal. Bit 6 works in the
opposite way, on = '0', off = '1' (safe stop input).
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/4
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/2
Bit 10-63
Reserved for future terminals
Table 6.11 Active Digital Inputs
D I T - 3 3
D I T - 3 2
D I T - 2 9
D I T - 2 7
D I T - 1 9
D I T - 1 8
D I T - 3 7
D I X 3 0/4
D I X 3 0/3
D I X 3 0/2
D I X 4 6/ 1 3
D I X 4 6/ 1 1
D I X 4 6/9
D I X 4 6/ 7
D I X 4 6/ 5
D I X 4 6/3
D I X 4 6/ 1
130BA894.10
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
Figure 6.21 Relay Settings
16-61 Terminal 53 Switch Setting
Option:
Function:
View the setting of input terminal 53.
[0]
Current
[1]
Voltage
16-62 Analog Input 53
Range:
Function:
0
*
[-20 - 20 ]
View the actual value at input 53.
16-63 Terminal 54 Switch Setting
Option:
Function:
View the setting of input terminal 54.
[0]
Current
[1]
Voltage
16-64 Analog Input 54
Range:
Function:
0
*
[-20 - 20 ]
View the actual value at input 54.
16-65 Analog Output 42 [mA]
Range:
Function:
0
*
[0 - 30 ] View the actual value at output 42 in mA. The
value shown reflects the selection in
parameter 6-50 Terminal 42 Output
.
16-66 Digital Output [bin]
Range:
Function:
0
*
[0 - 15 ]
View the binary value of all digital outputs.
16-67 Pulse Input #29 [Hz]
Range:
Function:
0
*
[0 - 130000 ] View the actual frequency rate on terminal
29.
16-68 Freq. Input #33 [Hz]
Range:
Function:
0
*
[0 - 130000 ] View the actual value of the frequency
applied at terminal 33 as an impulse input.
16-69 Pulse Output #27 [Hz]
Range:
Function:
0
*
[0 - 40000 ] View the actual value of pulses applied to
terminal 27 in digital output mode.
16-70 Pulse Output #29 [Hz]
Range:
Function:
0
*
[0 - 40000 ] View the actual value of pulses at terminal 29
in digital output mode.
16-71 Relay Output [bin]
Range:
Function:
0
*
[0 - 511 ]
View the settings of all relays.
Figure 6.23 Relay Settings
Parameter Descriptions
Operating Instructions
MG34M422
Danfoss A/S © Rev. 2013-07-03 All rights reserved.
109
6
6
Содержание VLT CDS 303
Страница 2: ......