Parameter
Setting
Notes
Parameter 13-00 SL Controller
Mode
On
TRUE
FALSE
Parameter 13-40 Logic Rule
Boolean 1 [0]
[37] Digital
Input DI32
Parameter 13-42 Logic Rule
Boolean 2 [0]
[2] Running
Parameter 13-41 Logic Rule
Operator 1 [0]
[3] AND
NOT
Parameter 13-40 Logic Rule
Boolean 1 [1]
[37] Digital
Input DI32
Parameter 13-42 Logic Rule
Boolean 2 [1]
[2] Running
Parameter 13-41 Logic Rule
Operator 1 [1]
[1] AND
Parameter 13-15 RS-FF
Operand S [0]
[26]
Logicrule 0
Output from 13-41
[0]
Parameter 13-16 RS-FF
Operand R [0]
[27]
Logicrule 1
Output from 13-41
[1]
Parameter 13-51 SL Controller
Event [0]
[94] RS
Flipflop 0
Output from
evaluating 13-15
and 13-16
Parameter 13-52 SL Controller
Action [0]
[22] Run
Parameter 13-51 SL Controller
Event [1]
[27]
Logicrule 1
Parameter 13-52 SL Controller
Action [1]
[24] Stop
Table 6.9 Operators
13-15 RS-FF Operand S
Option:
Function:
[0]
FALSE
[1]
TRUE
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
13-15 RS-FF Operand S
Option:
Function:
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reverse
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Timeout 0
[31]
SL Timeout 1
[32]
SL Timeout 2
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
[38]
Digital input DI33
[39]
Start command
[40]
Drive stopped
[41]
Reset Trip
[42]
Auto-reset Trip
[43]
OK key
[44]
Reset key
[45]
Left key
[46]
Right key
[47]
Up key
[48]
Down key
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Timeout 3
[71]
SL Timeout 4
[72]
SL Timeout 5
[73]
SL Timeout 6
[74]
SL Timeout 7
[75]
Start command given
[76]
Digital input x30/2
[77]
Digital input x30/3
[78]
Digital input x30/4
[79]
Digital input x46/1
Parameter Descriptions
VLT
®
Compressor Drives CDS 302/CDS 303
92
Danfoss A/S © Rev. 2013-07-03 All rights reserved.
MG34M422
6
6
Содержание VLT CDS 303
Страница 2: ......