Recommended max. fuse
Power
[kW]
Bussmann
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
Type JFHR2
1)
JFHR2
JFHR2
2)
J
11
FWX-80
-
-
HSJ-80
15-18.5
FWX-125
-
-
HSJ-125
22
FWX-150
L25S-150
A25X-150
HSJ-150
30
FWX-200
L25S-200
A25X-200
HSJ-200
37
FWX-250
L25S-250
A25X-250
HSJ-250
Table 3.12 200-240 V, Frame Sizes B and C
1)
FWH-fuses from Bussmann may substitute FWX for 240 V frequency converters.
2)
A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V frequency converters.
Recommended max. fuse
Power
[kW]
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Type RK1
Type J
Type T
Type CC
Type CC
Type CC
11
KTS-R-40
JKS-40
JJS-40
-
-
-
15
KTS-R-50
JKS-50
JJS-50
-
-
-
18
KTS-R-60
JKS-60
JJS-60
-
-
-
22
KTS-R-80
JKS-80
JJS-80
-
-
-
30
KTS-R-100
JKS-100
JJS-100
-
-
-
37
KTS-R-125
JKS-125
JJS-125
-
-
-
45
KTS-R-150
JKS-150
JJS-150
-
-
-
55
KTS-R-200
JKS-200
JJS-200
-
-
-
75
KTS-R-250
JKS-250
JJS-250
-
-
-
Table 3.13 380-500 V, Frame Sizes B and C
Recommended max. fuse
Power
[kW]
SIBA
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
Type RK1
Type RK1
Type CC
Type RK1
11
5014006-040
KLS-R-40
-
A6K-40-R
15
5014006-050
KLS-R-50
-
A6K-50-R
18
5014006-063
KLS-R-60
-
A6K-60-R
22
2028220-100
KLS-R-80
-
A6K-80-R
30
2028220-125
KLS-R-100
-
A6K-100-R
37
2028220-125
KLS-R-125
-
A6K-125-R
45
2028220-160
KLS-R-150
-
A6K-150-R
55
2028220-200
KLS-R-200
-
A6K-200-R
75
2028220-250
KLS-R-250
-
A6K-250-R
Table 3.14 380-500 V, Frame Sizes B and C
How to Install
VLT
®
Compressor Drives CDS 302/CDS 303
32
Danfoss A/S © Rev. 2013-07-03 All rights reserved.
MG34M422
3
3
Содержание VLT CDS 303
Страница 2: ......