![background image](http://html1.mh-extra.com/html/danfoss/vlt-automationdrive/vlt-automationdrive_operating-instructions-manual_3430207070.webp)
Mains Supply 3 x 525 - 600V AC
FC 302
P37K
P45K
P55K
P75K
High/
Normal
Load*
HO
NO
HO
NO
HO
NO
HO
NO
Typical Shaft Output [kW]
37
45
45
55
55
75
75
90
Enclosure IP21, 55, 66
C1
C1
C1
C2
C2
Enclosure IP20
C3
C3
C3
C4
C4
Output current
Continuous
(3 x 525-550V) [A]
54
65
65
87
87
105
105
137
Intermittent
(3 x 525-550V) [A]
81
72
98
96
131
116
158
151
Continuous
(3 x 525-600V) [A]
52
62
62
83
83
100
100
131
Intermittent
(3 x 525-600V) [A]
78
68
93
91
125
110
150
144
Continuous kVA (550V AC) [kVA]
51.4
61.9
61.9
82.9
82.9
100.0
100.0
130.5
Continuous kVA (575V AC) [kVA]
51.8
61.7
61.7
82.7
82.7
99.6
99.6
130.5
Max. input current
Continuous
at 550V [A]
49
59
59
78.9
78.9
95.3
95.3
124.3
Intermittent
at 550V [A]
74
65
89
87
118
105
143
137
Continuous
at 575V [A]
47
56
56
75
75
91
91
119
Intermittent
at 575V [A]
70
62
85
83
113
100
137
131
Additional specifications
Max. cable size IP20
(mains, motor)
[mm
2
(AWG
2)
)]
50 (1)
95 (4/0)
150 (300mcm)
Max. cable size IP20
(load share, brake)
[AWG]
2)
[mm
2
]
50 (1)
95 (4/0)
Max. cable size IP21, 55, 66
(mains, motor, load share and
brake)
[mm
2
(AWG
2)
)]
90 (3/0)
120 (4/0)
Max cable size with mains
disconnect
35 (2)
70 (3/0)
150 (300mcm)
Estimated power loss
at rated max. load [W]
4)
850
1100
1400
1500
Weight,
enclosure IP20 [kg]
35
35
50
50
Weight,
enclosure IP21, 55 [kg]
45
45
65
65
Efficiency
4)
0.98
0.98
0.98
0.98
Specifications
VLT
®
AutomationDrive Operating
Instructions
68
MG.33.AJ.02 - VLT
®
is a registered Danfoss trademark
10
0