Parameters
Function
Setting
8-30 Protocol
FC*
8-31 Address
1*
8-32 Baud Rate
9600*
* = Default Value
Notes/comments:
Select protocol, address and
baud rate in the above
mentioned parameters.
Table 6.11 RS-485 Network Connection
CAUTION
Thermistors must use reinforced or double insulation to
meet PELV insulation requirements.
Parameters
Function
Setting
1-90 Motor
Thermal
Protection
[2] Thermistor
trip
1-93 Thermistor
Source
[1] Analog
input 53
* = Default Value
Notes/comments:
If only a warning is desired,
1-90 Motor Thermal Protection
should be set to [1]
Thermistor
warning
.
Table 6.12 Motor Thermistor
Application Set-Up Examples
VLT
®
AutomationDrive Operating
Instructions