Analog inputs
Number of analog inputs
2
Terminal number
53, 54
Modes
Voltage or current
Mode select
Switch S201 and switch S202
Voltage mode
Switch S201/switch S202 = OFF (U)
Voltage level
0 to + 10 V (scaleable)
Input resistance, R
i
approx. 10 k
Ω
Max. voltage
±
20 V
Current mode
Switch S201/switch S202 = ON (I)
Current level
0/4 to 20 mA (scaleable)
Input resistance, R
i
approx. 200
Ω
Max. current
30 mA
Resolution for analog inputs
10 bit (+ sign)
Accuracy of analog inputs
Max. error 0.5% of full scale
Bandwidth
200 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Mains
Functional
isolation
PELV isolation
Motor
DC-Bus
High
voltage
Control
+24V
RS485
18
37
130BA117.10
Figure 8.13
Pulse inputs
Programmable pulse inputs
2
Terminal number pulse
29, 33
Max. frequency at terminal, 29, 33
110 kHz (push-pull driven)
Max. frequency at terminal, 29, 33
5 kHz (open collector)
Min. frequency at terminal 29, 33
4 Hz
Voltage level
see
Maximum voltage on input
28 V DC
Input resistance, R
i
approx. 4 k
Ω
Pulse input accuracy (0.1–1 kHz)
Max. error: 0.1% of full scale
Analog output
Number of programmable analog outputs
1
Terminal number
42
Current range at analog output
0/4–20 mA
Max. resistor load to common at analog output
500
Ω
Accuracy on analog output
Max. error: 0.8% of full scale
Resolution on analog output
8 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Specifications
VLT
®
AutomationDrive FC 302 Low Harmonic Drive
132–630 kW
96
Danfoss A/S © Rev. 04/2015 All rights reserved.
MG37A322
8
8