5.4.3 Commissioning via [Main Menu]
Recommended parameter settings are intended for start-
up and check-out purposes. Application settings may vary.
Enter data with power ON, but before operating the
adjustable frequency drive.
1.
Press [Main Menu] on the LCP.
2.
Press the navigation keys to scroll to parameter
group
0-** Operation/Display
and press [OK].
130BP066.10
1107 RPM
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
3.84 A
1 (1)
Main Menu
Figure 5.2 Main Menu
3.
Press the navigation keys to scroll to parameter
group
0-0* Basic Settings
and press [OK].
0-
**
Operation / Display
0.0%
0-0
*
Basic Settings
0-1
*
Set-up Operations
0-2
*
LCP Display
0-3
*
LCP Custom Readout
0.00A
1(1)
130BP087.10
Figure 5.3 Operation/Display
4.
Press the navigation keys to scroll to
parameter 0-03 Regional Settings
and press [OK].
0-0
*
Basic Settings
0.0%
0-03 Regional Settings
[0] International
0.00A
1(1)
130BP088.10
Figure 5.4 Basic Settings
5.
Press the navigation keys to select
[0] Interna-
tional
or
[1] North America
as appropriate and
press [OK]. (This changes the default settings for
a number of basic parameters).
6.
Press [Main Menu] on the LCP.
7.
Press the navigation keys to scroll to
parameter 0-01 Language
.
8.
Select the language and press [OK].
9.
If a jumper wire is in place between control
terminals 12 and 27, leave
parameter 5-12 Terminal 27 Digital Input
at factory
default. Otherwise, select
No Operation
in
parameter 5-12 Terminal 27 Digital Input
. For
adjustable frequency drives with an optional
bypass, no jumper wire is required between
control terminals 12 and 27.
10.
Make the application-specific settings in the
following parameters:
10a
Parameter 3-02 Minimum Reference
.
10b
Parameter 3-03 Maximum Reference
.
10c
Parameter 3-41 Ramp 1 Ramp-up Time
.
10d
Parameter 3-42 Ramp 1 Ramp-down Time
.
10e
Parameter 3-13 Reference Site
. Linked to
Hand/Auto Local Remote.
5.4.4 Asynchronous Motor Set-up
Enter the following motor data. The information can be
found on the motor nameplate.
1.
Parameter 1-20 Motor Power [kW]
or
parameter 1-21 Motor Power [HP]
.
2.
Parameter 1-22 Motor Voltage
.
3.
Parameter 1-23 Motor Frequency
.
4.
Parameter 1-24 Motor Current
.
5.
Parameter 1-25 Motor Nominal Speed
.
When running in flux mode, or for optimum performance
in VVC
+
mode, extra motor data is required to set up the
following parameters. The data can be found in the motor
datasheet (this data is typically not available on the motor
nameplate). Run a complete AMA using
parameter 1-29 Automatic Motor Adaptation (AMA)
[1]
Enable Complete AMA
or enter the parameters manually.
Parameter 1-36 Iron Loss Resistance (Rfe)
is always entered
manually.
1.
Parameter 1-30 Stator Resistance (Rs)
.
2.
Parameter 1-31 Rotor Resistance (Rr)
.
3.
Parameter 1-33 Stator Leakage Reactance (X1)
.
Start-up and Functional Tes...
Installation Manual
MG37A322
Danfoss A/S © Rev. 04/2015 All rights reserved.
57
5
5
Содержание VLT AutomationDrive FC 302
Страница 2: ......
Страница 127: ...Index Installation Manual MG37A322 Danfoss A S Rev 04 2015 All rights reserved 125...