The adjustable frequency drive is protected against ground faults on motor terminals U, V, W.
Frame size
D13
E9
F18
Voltage [V]
380–480
380–480
380–480
Current, RMS [A]
120
210
330
Nominal value
Peak current [A]
340
595
935
Amplitude value of the current
Response time [ms]
<0.5
Settling time - reactive current control [ms]
<40
Settling time - harmonic current control
(filtering) [ms]
<20
Overshoot - reactive current control [%]
<20
Overshoot - harmonic current control [%]
<10
Table 8.4 Power Ranges (LHD with AF)
Grid conditions
Supply voltage
380–480 V
AC line voltage low/line drop-out:
During low AC line voltage or a line drop-out, the filter continues until the intermediate circuit voltage drops below the minimum
stop level, which corresponds to 15% below the filter lowest rated supply voltage. Full compensation cannot be expected at AC
line voltage lower than 10% below the filter lowest rated supply voltage. If AC line voltage exceeds the filter highest rated
voltage, the filter continues to work but harmonic mitigation performance is reduced. The filter does not cut out until AC line
voltages exceed 580 V.
Supply frequency
50/60 Hz ±5%
Max. imbalance temporary between line phases
where mitigation performance is kept high.
3.0% of rated supply voltage
Filter mitigates at higher line imbalance but harmonic mitigation
performance is reduced
Max THDv pre-distortion
10% with kept mitigation performance
Reduced performance for higher pre-distortion levels
Harmonic mitigation performance
THiD
Best performance <4%
Depending on filter vs. distortion ratio.
Individual harmonic mitigation ability:
Current maximum RMS [% of rated RMS current]
2nd
10%
4th
10%
5th
70%
7th
50%
8th
10%
10th
5%
11th
32%
13th
28%
14th
4%
16th
4%
17th
20%
19th
18%
20th
3%
22nd
3%
23rd
16%
25th
14%
Total current of harmonics
90%
The filter is performance tested to the 40th order
Specifications
Installation Manual
MG37A322
Danfoss A/S © Rev. 04/2015 All rights reserved.
99