8.1.3 Line Power Supply 525–600 V (FC 302 only)
Type designation
PK75
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
Typical shaft output (hp [kW])
1.0 [0.75] 1.5 [1.1]
2 [1.5]
3 [2.2]
4 [3]
5 [4]
7.5 [5.5]
10 [7.5]
Enclosure protection rating IP20, IP21
A3
A3
A3
A3
A3
A3
A3
A3
Enclosure protection rating IP55
A5
A5
A5
A5
A5
A5
A5
A5
Output current
Continuous (525–550 V) [A]
1.8
2.6
2.9
4.1
5.2
6.4
9.5
11.5
Intermittent (525–550 V) [A]
2.9
4.2
4.6
6.6
8.3
10.2
15.2
18.4
Continuous (551–600 V) [A]
1.7
2.4
2.7
3.9
4.9
6.1
9.0
11.0
Intermittent (551–600 V) [A]
2.7
3.8
4.3
6.2
7.8
9.8
14.4
17.6
Continuous kVA (525 V) [kVA]
1.7
2.5
2.8
3.9
5.0
6.1
9.0
11.0
Continuous kVA (575 V) [kVA]
1.7
2.4
2.7
3.9
4.9
6.1
9.0
11.0
Maximum input current
Continuous (525–600 V) [A]
1.7
2.4
2.7
4.1
5.2
5.8
8.6
10.4
Intermittent (525–600 V) [A]
2.7
3.8
4.3
6.6
8.3
9.3
13.8
16.6
Additional specifications
Maximum cable cross-section
2)
for line power,
motor, brake and load sharing [mm
2
] ([AWG])
4,4,4 (12,12,12)
(min. 0.2 (24))
Maximum cable cross-section
2)
for disconnect
[mm
2
] ([AWG])
6,4,4 (10,12,12)
Estimated power loss at rated maximum load
(hp [W])
3)
0.047
[35]
0.067
[50]
0.087
[65]
0.123
[92]
0.164
[122]
0.195
[145]
0.262
[195]
0.350
[261]
Efficiency
4)
0.97
0.97
0.97
0.97
0.97
0.97
0.97
0.97
Table 8.7 Line Power Supply 525–600 V (FC 302 only), PK75-P7K5