ALARM 31, Motor phase V missing
Motor phase V between the adjustable frequency drive
and the motor is missing.
Troubleshooting
•
Remove the power from the adjustable frequency
drive and check motor phase V.
ALARM 32, Motor phase W missing
Motor phase W between the adjustable frequency drive
and the motor is missing.
Troubleshooting
•
Remove the power from the adjustable frequency
drive and check motor phase W.
ALARM 33, Inrush fault
Too many power-ups have occurred within a short time
period.
Troubleshooting
•
Let the unit cool to operating temperature.
WARNING/ALARM 34, Fieldbus communication fault
The serial communication bus on the communication
option card is not working.
WARNING/ALARM 35, Option fault
An option alarm is received. The alarm is option-specific.
The most likely cause is a power-up or a communication
fault.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to
the adjustable frequency drive is lost and
14-10 Mains
Failure
is not set to option
[0] No Function
. Check the fuses
to the adjustable frequency drive and line power supply to
the unit.
ALARM 37, Phase imbalance
There is a current imbalance between the power units.
ALARM 38, Internal fault
When an internal fault occurs, a code number defined in
is displayed.
Troubleshooting
•
Cycle power.
•
Check that the option is properly installed.
•
Check for loose or missing wiring.
It may be necessary to contact the Danfoss supplier or
service department. Note the code number for further
troubleshooting directions.
No.
Text
0
Serial port cannot be initialized. Contact the
Danfoss supplier or Danfoss Service Department.
256-258
Power EEPROM data is defective or too old.
Replace power card.
No.
Text
512-519
Internal fault. Contact the Danfoss supplier or
Danfoss Service Department.
783
Parameter value outside of minimum/maximum
limits.
1024-1284 Internal fault. Contact the Danfoss supplier or the
Danfoss Service Department.
1299
The option SW in slot A is too old.
1300
The option SW in slot B is too old.
1302
The option SW in slot C1 is too old.
1315
The option SW in slot A is not supported (not
allowed).
1316
The option SW in slot B is not supported (not
allowed).
1318
The option SW in slot C1 is not supported (not
allowed).
1379-2819 Internal fault. Contact the Danfoss supplier or
Danfoss Service Department.
1792
HW reset of DSP.
1793
Motor-derived parameters not transferred correctly
to DSP.
1794
Power data not transferred correctly at power-up
to DSP.
1795
The DSP has received too many unknown SPI
messages.
1796
RAM copy error.
2561
Replace control card.
2820
LCP stack overflow.
2821
Serial port overflow.
2822
USB port overflow.
3072-5122 Parameter value is outside its limits.
5123
Option in slot A: Hardware incompatible with
control board hardware.
5124
Option in slot B: Hardware incompatible with
control board hardware.
5125
Option in slot C0: Hardware incompatible with
control board hardware.
5126
Option in slot C1: Hardware incompatible with
control board hardware.
5376-6231 Internal fault. Contact the Danfoss supplier or
Danfoss Service Department.
Table 7.4 Internal Fault Codes
ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gate drive card, or the ribbon cable between the
power card and gate drive card.
Maintenance, Diagnostics an...