16-32 Brake Energy /s
Range:
Function:
0.000k
W
*
[0.000 - 0.000 kW]
View the brake power transmitted to an external brake resistor,
stated as an instantaneous value.
16-33 Brake Energy /2 min
Range:
Function:
0.000k
W
*
[0.000 - 500.000 kW] View the brake power transmitted to an external brake resistor.
The mean power is calculated on an average basis for the most
recent 120 seconds.
16-34 Heatsink Temp.
Range:
Function:
0°C
*
[0 - 255 °C]
View the frequency converter heatsink temperature. The cut-
out limit is 90 ± 5 °C, and the motor cuts back in at 60 ± 5 °C.
16-35 Inverter Thermal
Range:
Function:
0 %
*
[0 - 100 %]
View the percentage load on the inverter.
16-36 Inv. Nom. Current
Range:
Function:
A
*
[0.01 - 10000 A]
View the inverter nominal current, which should match the
nameplate data on the connected motor. The data are used for
calculation of torque, motor protection, etc.
16-37 nv. Max. Current
Range:
Function:
A
*
[0.01 - 10000 A]
View the inverter maximum current, which should match the
nameplate data on the connected motor. The data are used for
calculation of torque, motor protection, etc.
16-38 SL Controller State
Range:
Function:
0
*
[0 - 0]
View the state of the event under execution by the SL controller.
16-39 Control Card Temp.
Range:
Function:
0°C
*
[0 - 100 °C]
View the temperature on the control card, stated in °C.
16-40 Logging Buffer Full
Option:
Function:
[0]
*
No