Counter [9]: 90% - <100% or Max
The above minimum limits for the intervals are the default limits.
These can be changed in par. 23-65,
Minimum Bin Value
.
Starts to count when the frequency converter is powered up for
the first time. All counters can be reset to 0 in par. 23-66,
Reset
Continuous Bin Data
.
23-62 Timed Bin Data
Range:
Function:
0
*
[0-4294967295]
Array with 10 elements ([0]-[9] below parameter number in
display). Press OK and step between elements by means of
▲
and
▼
buttons on the LCP.
10 counters with the frequency of occurrence for the operating
data monitored sorted according to the intervals as for par.
23-61,
Continuous Bin Data
.
Starts to count at the date/time programmed in par. 23-63,
Timed Period Start
, and stops at the time/date programmed in
par. 23-64,
Timed Period Stop
. All counters can be reset to 0 in
par. 23-67,
Reset Timed Bin Data
.
23-63 Timed Period Start
Range:
Function:
2000-01
-01
00:00
*
[2000-01-01 00:00 -
2099-12-31 23:59]
Set the date and time at which the Trending starts the update
of the Timed Bin counters.
Date format will depend on setting in par. 0-71,
Date Format
,
and time format on setting in par. 0-72,
Time Format
.
NB!
The frequency converter has no back up of the
clock function and the set date/time will reset to
default (2000-01-01 00:00) after a power down
unless a Real Time Clock module with back up is
installed. Consequently the logging will be stop-
ped until date/time is readjusted in par. 0-70,
Set
Date and Time
. In par. 0-79,
Clock Fault
, it is pos-
sible to program for a Warning in case clock not
has been set properly, e.g. after a power down.
23-64 Timed Period Stop
Range:
Function:
2000-01
-01
00:00
*
[2000-01-01 00:00 -
2099-12-31 23:59]
Set the date and time at which the Trend Analyses must stop
update of the Timed Bin counters.
Date format will depend on setting in par. 0-71,
Date Format
,
and time format on setting in par. 0-72,
Time Format
.
2. Parameter Description
VLT
®
AQUA Drive Programming Guide
224
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
2