Illustration 3.6 Enclosures B (except B3) and C
How to add the MCO 102 option
1.
Disconnect power.
2.
Disconnect power to the live part connections on
relay terminals.
3.
Remove the LCP, the terminal cover and the
cradle from the FC 202.
4.
Fit the MCO 102 option in slot C1.
5.
Connect the control cables and relief the cables
by the enclosed cable strips.
6.
Fit the extended cradle and terminal cover.
7.
Remount the LCP.
8.
Connect power to the frequency converter.
Wiring the Terminals
130BB025.11
Illustration 3.7 Advanced Cascade Controller MCO 102
Terminal Connections, 8 Relays
130BB026.11
Illustration 3.8 Advanced Cascade Controller MCO 102
Terminal Connections to the 7 Digital Inputs and Access to
the Internal 24 V DC