3 Installation
3.1 Mechanical and Electrical Installation
3.1.1 Before Start
NOTICE
Before start, interrupt the power supply to the frequency
converter. Never install an option card into the
frequency converter during operation.
Voltage
[V]
Minimum Waiting Time (Minutes)
4
7
15
20
200-240
0.25-3.7 kW
5.5-45 kW
380-480
0.37-7.5 kW
11-90 kW
525-600
0.75-7.5 kW
11-90 kW
525-690
1.1-7.5 kW
11-90 kW
3x400
90-250 kW
3x400
110-315 kW
3x500
110-315 kW
3x500
132-355 kW
3x525
75-250 kW
3x525
90-315 kW
3x690
90-250 kW
3x690
110-315 kW
High voltage may be present even when the warning
LED display lights are off.
Table 3.1 Discharge Time
NOTICE
Export Control
From software version 6.72 the output of the frequency
converter is limited to 590 Hz. Software version 6x.xx is a
special software for export to countries where special
legislation for export control applies. In this version the
output of the frequency converter is also limited to 590
Hz, the difference from standard software is that it
cannot be flashed, i.e. neither downgraded nor
upgraded.
3.1.2 Extended Cascade Controller
MCO 101
The MCO 101 option includes 3 pieces of change-over
contacts and can be fitted into option slot B.
Max terminal load (AC)
240 V AC 2 A
Max terminal load (DC)
24 V DC 1 A
Min terminal load (DC)
5 V 10 mA
Max switching rate at rated load/min load
6 min
-1
/20 s
-1
Table 3.2 Electrical Data
130BA607.11
MC
O 101
1
Illustration 3.1 Mounting of B Options
1
Dismount MCO 101 option to access RS-485 termination
(S801) or current/voltage switches (S201, S202)
Table 3.3
How to add the MCO 101 option:
1.
Disconnect power to the frequency converter.
2.
Disconnect power to the live part connections on
relay terminals.
3.
Remove the LCP, the terminal cover and the
cradle from the FC 202.
4.
Fit the MCO 101 option in slot B.
5.
Connect the control cables and relief the cables
by the enclosed cable strips.
6.
Fit the extended cradle and terminal cover.
7.
Remount the LCP.
8.
Connect power to the frequency converter.
Installation
VLT
®
AQUA Drive MCO 101/MCO 102
12
MI38C402 - VLT
®
is a registered Danfoss trademark
3