VLT® 7000 Booster
Programming
Function:
In addition to its normal function, this parameter
can be used for two different tests.
Furthermore, it is possible to reset to the default
factory settings for all Setups, except parameters
500
Address
, 501 Baud rate, 600-605
Operating
data
and 615-617
Fault log
.
Description of choice:
Normal function
[0] is used for normal
operation of the motor.
Function with
de-activated inverter
[1] is selected if
control is desired over the influence of the control
sig-nal on the control card and its functions -
without the motor shaft running.
Control card
[2] is selected if control of the analogue
and digital inputs, analogue and digital outputs, relay
outputs and the control voltage of +10 V is desired.
A test connector with internal connections
is required for this test.
The test connector for the
Control card
[2]
is set up as follows:
connect
4-16-17-18-19-27-29-32-33;
connect
5-12;
connect
39-20-55;
connect
42 - 60;
connect
45-53-54.
Use the following procedure for the control card test:
1. Select
Control card test
.
2. Cut off the mains supply and wait for the
light in the display to go out.
3. Insert the test plug (see preceding column).
4. Connect to mains.
5. The frequency converter expects the [OK] key to be
pressed (the test cannot be run without LCP).
6. The frequency converter automatically tests
the control card.
7. Remove the test connector and press the [OK]
key when the frequency converter displays
"TEST COMPLETED".
8. Parameter 620
Operating mode
is automatically
set to
Normal function
.
If the control card test fails, the frequency conver-ter
will display "TEST FAILED". Replace the control card.
Initialisation
[3] is selected if the factory setting
of the unit is to be generated without resetting
parameters 500
Address
, 501
Baud rate
, 600-605
Operating data
and 615-6171
Fault log
.
Procedure for initialisation:
1. Select
Initialisation
.
2. Press the [OK] key.
3. Cut off the mains supply and wait for the
light in the display to go out.
4. Connect to mains.
5. Initialisation of all parameters will be carried out
in all Setups with the exception of parameters
500
Address
, 501
Baud rate
, 600-605
Operating
data
and 615-617
Fault log
.
Manual initialisation is another option. (See
Manual initialisation
).
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.70.A1.02 - VLT is a registered Danfoss trademark
91