VLT® 7000 Booster
■
Quick Menu
The QUICK MENU key gives access to 41 of
the most important setup parameters of the
drive. After programming, the drive will, in many
cases, be ready for operation.
Quick Menu
Number
Parameter
number
Name
Units
Range
Factory Setting
1
102
Motor Power
KW/HP
1,1-55/1,5-75
kW
2
103
Motor Voltage
Volt
380-460
3
104
Motor Frequency
Hz
50/60 Hz
50 Hz
4
105
Motor Current
Amps
0-Ivlt,max
-
5
106
Rated motor speed
RPM
1200 - f m,n x 60
-
6
201
Min. Frequency
Hz
0,0 - fmax
20 Hz
7
202
Max. Frequency
Hz
fmin - 120/1000
50 Hz
8
206
Ramp up time
seconds
1-60
See table below
9
207
Ramp down time
Seconds
1-60
See table below
10
415
Pressure unit
Bar
11
413
Minimum Feedback
Par. 415
999.999,999-FBmax
0.000
12
414
Maximum Feedback
Par. 415
FBmin - 999.999,999
100.000
13
227
Warning Low Feedback
Par. 415
999.999,999-FBhigh
-999.999.999
14
228
Warning High Feedback
Par. 415
FBlow - 999.999,999
999.999.999
15
204
Minimum reference
Par. 415
Min. feedback - Max. reference
0.000
16
205
Maximum reference
Par. 415
Min. reference - Max. feedback
50.000
17
700
Cascade mode
1-14
1
18
701
Pump Combination
DOM
1
19
702
Staging bandwidth
%
0-100
5
20
703
SBW destage delay
Sec.
0-3000
10
21
704
SBW stage delay
Sec.
0-3000
10
22
705
Override bandwidth
%
0-100 (100=Off)
Off
23
706
Override timer
Sec.
0-300
10
24
707
Destage by timer
Sec.
0-301 (301=Off)
Off
25
708
Staging frequency
%
0-100% of f
max
90
26
709
Destaging frequency
%
0-100% of f
max
50
27
710
Delay before running on mains
ms
0-2000
500
28
711
Sleep/AUX timer
Sec.
0-300 (301 = Off)
DOM
2
29
712
Sleep/AUX frequency
Hz
Par. 201 - Par. 713
20 Hz
30
713
Wakeup/disable AUX -
frequency
Hz
Par. 712 - Par. 202
50 Hz
31
714
Boost setpoint
%
1-200% of Setpoint 1
100%
32
418
Setpoint 1 (H0)
Par. 415
Par. 413-Par. 414
0.000
33
419
Setpoint 2 (H1)
Par. 415
Par. 413-Par. 414
0.000
34
719
Pump enable
Indexed par.
0-1
1
35
720
Pump running hours
Hours
0,0-999.999,9
-
36
721
Setpoints
Par. 415
0,0-999.999,9
-
37
420
Normal/inverse control
Normal/inverse
Normal
38
422
PID start up frequency
Hz
f
min
- f
max
0
39
427
PID Lowpass filter time
Sec.
0.01-10.00
0.2
40
423
PID Proportional Gain
Factor
0.00-10.00
0.3
41
424
PID Integrator time
Sec.
0.01-9999.00
Off
VLT Type
Ramp up time
(par.206)
Ramp down time
(par.207)
7002-7011
1 sec.
1 sec.
7016-7062
3 sec.
2 sec.
7072
5 sec.
3 sec.
1) Depending on Mode, please refer to par. 700.
2) Depending on Mode, with AUX pump: 150
sec., without AUX pump: OFF.
MG.70.A1.02 - VLT is a registered Danfoss trademark
46
Содержание VLT 7000 Series
Страница 13: ...VLT 7000 Booster Introduction to Booster Ordering form MG 70 A1 02 VLT is a registered Danfoss trademark 13...
Страница 22: ...VLT 7000 Booster Mechanical dimensions MG 70 A1 02 VLT is a registered Danfoss trademark 22...
Страница 30: ...VLT 7000 Booster MG 70 A1 02 VLT is a registered Danfoss trademark 30...