VLT® 7000 Booster
Auxiliary pump/sleep
mode
■
Quick Menu 30 Par. 713 Wake up/disable
aux - frequency
Par. 713
Wake up/disable aux - frequency
(WAKEUP/DIS.AUX F)
Value:
Par. 712 Sleep frequency - par. 202 F
max
✭
50 Hz
Function:
When the theoretical output frequency exceeds the
preset value, the lead pump restarts, thereby switching
of the AUX pump if a such is being used.
Description of choice:
Set the required frequency.
■
Quick Menu 31 Par. 714 Boost setpoint
Par. 714 Boost setpoint
(BOOST SETPOINT)
Value:
0 - 200%
✭
100% of setpoint
Function:
In systems with constant pressure control, it is
advantageous to increase the pressure in the system
before the lead pump stops. This helps to avoid
frequent starting and stopping, e.g. in the case
of leaks in the water supply system.
Description of choice:
Set the required Boost setpoint as a percentage
of the resulting reference under normal operation.
100% corresponds to the reference without
boost (supplement).
MG.70.A1.02 - VLT is a registered Danfoss trademark
105