VLT® 7000 Booster
All about VLT 7000
Booster
The control unit attempts to correct the ramp if possible.
The inverter turns off to protect the transistors
and the intermediate circuit capacitors when a
certain voltage level is reached.
Mains drop-out
During a mains drop-out, VLT 7000 Booster continues
until the intermediate circuit voltage drops below the
minimum stop level, which is typically 15% below VLT
7000 Booster
’
s lowest rated supply voltage.
The time before the inverter stops depends on the mains
voltage before the drop-out and on the motor load.
Static overload
When VLT 7000 Booster is overloaded (the current
limit in parameter 215
Current limit
, I
LIM
has been
reached), the controls will reduce the output frequency
in an attempt to reduce the load.
If the overload is excessive, a current may
occur that makes the frequency converter cut
out after approx. 1.5 sec.
Operation within the current limit can be limited in time
(0-60 s) in parameter 412
Trip delay overcurrent, I
LIM
.
MG.70.A1.02 - VLT is a registered Danfoss trademark
119
Содержание VLT 7000 Series
Страница 13: ...VLT 7000 Booster Introduction to Booster Ordering form MG 70 A1 02 VLT is a registered Danfoss trademark 13...
Страница 22: ...VLT 7000 Booster Mechanical dimensions MG 70 A1 02 VLT is a registered Danfoss trademark 22...
Страница 30: ...VLT 7000 Booster MG 70 A1 02 VLT is a registered Danfoss trademark 30...