VLT® 7000 Booster
PNU
Parameter
Factory setting
Range
Changes
4-Setup
Conversion
Data
#
description
during operation
index
type
200
Output frequency range
0 - 120 Hz
0 - 1000 Hz
No
Yes
0
5
201
Output frequency low limit, f
MIN
0.0 Hz
0.0 - f
MAX
Yes
Yes
-1
6
202
Output frequency high limit, f
MAX
50 Hz
f
MIN
- par. 200
Yes
Yes
-1
6
203
Reference site
Hand/Auto linked reference
Yes
Yes
0
5
204
Minimum reference, Ref
MIN
0.000
0.000-par. 100
Yes
Yes
-3
4
205
Maximum reference, Ref
MAX
50.000
par. 100-999.999,999
Yes
Yes
-3
4
206
Ramp-up time
Depends on the unit
1 - 3600
Yes
Yes
0
7
207
Ramp-down time
Depends on the unit
1 - 3600
Yes
Yes
0
7
208
Automatic ramp-up/down
Enable
Yes
Yes
0
5
209
Jog frequency
10.0 Hz
0.0 - par. 100
Yes
Yes
-1
6
215
Current limit, l
LIM
1.0 x l
VLT,N[A]
0,1-1,1 x l
VLT,N[A]
Yes
Yes
-1
6
216
Frequency bypass, bandwidth
0 Hz
0 - 100 Hz
Yes
Yes
0
6
217
Frequency bypass 1
120 Hz
0.0 - par.200
Yes
Yes
-1
6
218
Frequency bypass 2
120 Hz
0.0 - par.200
Yes
Yes
-1
6
219
Frequency bypass 3
120 Hz
0.0 - par.200
Yes
Yes
-1
6
220
Frequency bypass 4
120 Hz
0.0 - par.200
Yes
Yes
-1
6
221
Warning: Low current, l
LOW
0.0 A
0.0 - par.222
Yes
Yes
-1
6
222
Warning: High current, l
HIGH
l
VLT,MAX
Par.221 - l
VLT,MAX
Yes
Yes
-1
6
223
Warning: Low frequency, f
LOW
0.0 Hz
0.0 - par.224
Yes
Yes
-1
6
224
Warning: High frequency, f
HIGH
120.0 Hz
Par.223 - par.200/202
Yes
Yes
-1
6
225
Warning: Low reference, Ref
LOW
-999,999.999
-999,999.999 - par.226
Yes
Yes
-3
4
226
Warning: High reference,
Ref
HIGH
999,999.999
Par.225 - 999,999.999
Yes
Yes
-3
4
227
Warning: Low feedback, FB
LOW
-999,999.999
-999,999.999 - par.228
Yes
Yes
-3
4
228
Warning: High feedback, FB
HIGH
999,999.999
Par. 227 - 999,999.999
Yes
Yes
-3
4
Changes during operation:
"Yes" means that the parameter can be changed,
while the frequency converter is in operation. "No"
means that the frequency converter must be stopped
before a change can be made.
4-Setup:
"Yes" means that the parameter can be programmed
individually in each of the four setups, i.e. the
same parameter can have four different data
values. "No" means that the data value will be
the same in all four setups.
Conversion index:
This number refers to a conversion figure to
be used when writing or reading by means
of a frequency converter.
Conversion index
Conversion factor
74
0.1
2
100
1
10
0
1
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
Data type:
Data type shows the type and length of the telegram.
Data type
Description
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Text string
MG.70.A1.02 - VLT is a registered Danfoss trademark
134
Содержание VLT 7000 Series
Страница 13: ...VLT 7000 Booster Introduction to Booster Ordering form MG 70 A1 02 VLT is a registered Danfoss trademark 13...
Страница 22: ...VLT 7000 Booster Mechanical dimensions MG 70 A1 02 VLT is a registered Danfoss trademark 22...
Страница 30: ...VLT 7000 Booster MG 70 A1 02 VLT is a registered Danfoss trademark 30...