manualshive.com logo in svg
background image

39

When the energy returned, combined with the DC Bus voltage, exceeds
the upper voltage limit, the unit responds in different ways to limit the
voltage rise.  If the returned energy is occurring during ramp down (to
stop or to a lower speed), the unit will automatically adjust the decel
ramp in an attempt to limit the voltage.  In more sever instances, the
ramp may even stop for periods of time to allow the voltage to dissipate.
During these periods while regeneration is occurring, the words "HIGH
VOLTAGE" can be observed flashing in the control card display.  If the
returned energy is returned at a high enough level and/or so fast that
the unit cannot respond, the unit will trip on "OVERVOLTAGE".

To prevent a trip from occurring, one solution is to lengthen the decel
ramp.  In applications with very high inertia loads, or in the case of
such loads as flywheels, the only solution may be that of adding a
Dynamic Brake option.

The Dynamic Brake option combines a power IGBT, the electronics for
controlling it and a resistor bank of sufficient wattage to dissipate the
unwanted energy.  The Dynamic Brake option monitors the level of the
DC Bus voltage.  When the voltage level exceeds permissible limits,
the IGBT is switched on and the excess DC Bus voltage is dissipated
in the resistor bank.

Particular attention must be paid to the proper sizing of the resistor
bank.  Consult your local representative or the factory for assistance in
selecting the appropriate Dynamic Brake option for your application.

Trips due to "OVERTEMP" can be due to internal or external over
temperature conditions. Two temperature sensors are located inside
of the drive. One located on the Interface Board monitors the ambient
temperature within the drive itself. This normally open switch closes at
a temperature of 73 to 87 degrees centigrade. The switch will reset at
a temperature between 53 to 67 degrees centigrade allowing a fault
reset to be possible. A fault occuring as a result of the ambient
temperature switch results in both the "IOT" and the "OTT" LED being
illuminated on the Interface Board and the Control card will display
"OVERTEMP". The second sensor located on the heatsink monitors
the surface temperature of the heatsink. This sensor is a NTC device
which changes in resistance value based on temperature. As the
temperature rises the resistance decreases, and conversely as the
temperature decreases the resistance increases. The sensors
resistance must be between 787 ohms and 105 K ohms to be free of a
fault condition. Testing this sensor is explained on page 27. A fault
occuring as a result of the NTC sensor results in the "OTT" LED on the
Interface Board being illuminated and the Control Card will display
"OVERTEMP". These temperature faults can be caused by high ambient
temperatures, clogged fan filters or inoperative cooling fans. The
heatsink and the door fans operate on 24VDC supplied by the Interface
Board.

"OVERVOLTAGE" TRIPS DUE TO
REGENERATIVE APPLICATIONS
(CONTINUED)

"OVERTEMP" TRIPS

Содержание VLT 3032

Страница 1: ...ectifiers 30 Testing for Current Feedback 30 Removing and Replacing the Control Card 31 Removing and Replacing the Interface Board 31 Removing and Replacing Gate Snubber IGBT 32 Removing and Replacing...

Страница 2: ...ting charts both in the form of flow and symptom cause Section three describes the various tests and methods used to evaluate the drives condition Section four covers the removal and replacement of th...

Страница 3: ...cal parts of the AFD when the AC line is connected After theAC line is disconnected wait at least 15 minutes before touching any of the components 2 When repairs or inspection is made the AC line must...

Страница 4: ...4...

Страница 5: ...he logic section is the keyboard display mounted on the control card The keyboard provides the interface between the digital logic and the human programmer The LCD Liquid Crystal Display provides the...

Страница 6: ...nstalled which can only be activated through the use of a normal remote control start In the same sense that the control card can only respond to commands comes the situation that the control card mak...

Страница 7: ...de supply is that it obtains its power from the DC Bus in the event of a power loss the power supply remains active for a longer period of time versus conventional power supplies During the troublesho...

Страница 8: ...sible through the shield covering the lower portion of the interface board and as long as it is lit it indicates the DC Bus voltage is greater than 50VDC A fault in the power section will usually resu...

Страница 9: ...s proceeds normally the power supplies will come up and provide the control card and all other sections of the unit with low voltage control power At this time the display in the control card will ind...

Страница 10: ...t condition CURRENT LIMIT This message will flash in the display when the unit is operating above the current limit setting as recorded in parameter 209 Parameter 310 may be set to provide a fixed tim...

Страница 11: ...At an inverter ETR value of 100 the unit trips on Invert Time MOTOR TIME This message will flash if Motor Thermal Protection has been activated in parameter 315 and the motor ETR value has reached 98...

Страница 12: ...will be out This fault returns a Trip Locked Also see Testing The Inverter Section page 26 OVER VOLTAGE 2 This message indicates the DC Bus voltage upper limit has been exceeded In addition the High...

Страница 13: ...rature condition This fault returns a Trip Also see Overtemp Trips page 39 INVERT TIME 7 This message indicates the unit has delivered greater than 105 of the unit s continuous current rating for too...

Страница 14: ...a Ground Fault on the Inverter Output The I0K LED will be off and the control card will indicate Ground Fault OVER TEMP TRIP OTT D3 RED Indicates the heatsink temperature is outside of the specified...

Страница 15: ...MK15 on the interface board The I0K LED will be off and the control card will indicate Over Temp POWER SUPPLY FAULT PSF D1 RED Indicates the low voltage power supplies are out of tolerance The I0K LE...

Страница 16: ...on the drive is with the motor disconnected In this way a faulty component that was overlooked or the unfortunate slip of a test probe will generally result in a unit trip instead of a component failu...

Страница 17: ...YES page 20 See 9 Refer to the section Alarm Messages page 13 7 Is the correct mains supply present at R S T NO YES Also see Section Applications pg 35 3 See Testing the Inverter Section page 26 2 Is...

Страница 18: ...re of the fuses F4 F5 or F6 have blown test the soft charge circuit page 23 NO YES 13 The fault may be caused by a short circuit in the control signals Check control wiring for proper connection NO YE...

Страница 19: ...ated Is the unit properly grounded to earth NO YES Consult factory 26 Replace the Interface ILD card see page 31 Does the motor run YES NO 23 Attempt to run the VLT in local SEE CAUTION at LEFT Make t...

Страница 20: ...otor One inverter phase missing Test output phase balance page 27 One half of one inverter phase missing Test output phase balance page 27 6 Motor Runs Unloaded But Stalls When Loaded Motor may run ro...

Страница 21: ...Input line voltage unbalanced Faulty connection on input wiring Fault in plant power transformer Input SCR Diode module faulty or not being gated Open motor winding Faulty motor connection Fault in in...

Страница 22: ...circuit is to rule out failures of the Soft Charge Rectifier and Soft Charge Resistors If the soft charge fuses have blown it indicates the possibility of a short circuit of the DC Bus A DC Bus short...

Страница 23: ...lead to the soft charge fuses F4 F5 and F6 in turn Each reading should show a diode drop 5 Connect the positive meter lead to the negative terminal of the rectifier Connect the negative meter lead to...

Страница 24: ...Each reading should show open 3 Reverse the meter leads connecting the lead to terminal 89 VDC and the lead to terminals 91 R 92 S and 93 T in turn Each reading should show a diode drop 4 Connect the...

Страница 25: ...turn Each reading should show a diode drop 4 Connect the positive meter lead to terminal 88 VDC Connect the negative meter lead to terminals 96 U 97 V and 98 W in turn Each reading should show a diod...

Страница 26: ...on within the unit itself This can be caused by improper gate drive signals as a result of a faulty interface board or gate drive board A faulty IGBT or loose wire connection between the IGBT and the...

Страница 27: ...e the test points are the same This test can be made at the interface board or at each gate card output to its respective IGBT These tests can be made with or without a motor However it is generally s...

Страница 28: ...at the gate driver requires that the test leads are connected and then the unit is reassembled to conduct the tests Extreme care must be taken to insure test leads can not come in contact with other p...

Страница 29: ...t is proportional to the current being drawn in each respective phase The VLT relies on this feedback for proper waveform control and for providing fault protection A simple test of the signals can be...

Страница 30: ...ed to insure they can be returned to the correct location 3 Working around the board release the 11 swag clips with the use of needle nose pliers Gently lift the board clear of the swags as you go 4 I...

Страница 31: ...and the Motor Coil Wire to the IGBT to be replaced 6 Loosen the remaining Standoffs but do not remove on the remaining two IGBT s This should allow sufficient clearance to slide the IGBT from beneath...

Страница 32: ...s to 18 22 LB IN 2 03 2 49 NM Insure the bus sensing wire marked K is secured to the lower bus bar 9 Install the Phillips screw securing the line connection to the module Torque to 18 22 LB IN 2 03 2...

Страница 33: ...rt Compensation 209 Current Limit Parameter 100 An incorrect setting may provide an improper voltage to frequency ratio to the motor with respect to the load demand For example a constant torque CT lo...

Страница 34: ...t voltage If multiple motors are connected to a single unit it is usually necessary to increase the start voltage Smaller motors have greater voltage drops at low frequencies so additional start volta...

Страница 35: ...nd all associated wiring and connections are captured in the test When reading the results of the Megger test the rule of thumb is any reading less than 500 Megohms should be suspect Solid dry wiring...

Страница 36: ...on process from there The amount of current required may be so great and rise so rapidly that the current limit function cannot control the process The result is an OVERCURRENT trip However this situa...

Страница 37: ...ative or the factory for assistance in selecting the appropriate Dynamic Brake option for your application Trips due to OVERTEMP can be due to internal or external over temperature conditions Two temp...

Страница 38: ...rminals 1 and 2 of MK15 When MK15 is activated the result is a fault trip with the OTT and EOT LED s on the Interface Board being illuminated The Control Card will display OVERTEMP An EOT fault also d...

Страница 39: ...addition there are six more codes which may appear in parameter 602 10 Trip Locked Indicates a trip lock fault has occurred 11 CT OP Card Fault Indicates a software fault has occurred in either the C...

Страница 40: ...Fuse 175L3830 Soft Charge Fuse 175L3829 Soft Charge Rectifier 175L3832 Input Rectifier 175L3831 Soft Charge Resistor Assembly 175L3833 IGBT Module 3032 175L3836 IGBT Module 3042 52 175L3837 Power Supp...

Страница 41: ...III...

Страница 42: ...IV...

Страница 43: ...V...

Отзывы: