Ramp 2
is selected if a shift between ramp 1
(parameters
207-208)
and ramp 2
(parameters 209-210)
is required.
Logic '0' leads to ramp 1 and logic '1' leads to ramp 2.
Preset reference, lsb
and
Preset reference, msb
make it
possible to select one of the 4 preset references in
Preset ref. msb
Preset ref. lsb
Function
0
0
Preset ref. 1
0
1
Preset ref. 2
1
0
Preset ref. 3
1
1
Preset ref. 4
Table 4.5 Function of Present Reference lsb and msb
Preset reference on
is used for shifting between remote-
controlled reference and preset reference. It is assumed
that
[2] External/preset
has been selected in
parameter 214
Reference function
. Logic '0' = remote-controlled references
are active, logic '1' = one of the 4 preset references is
active, as shown in
Select
Thermistor
if a possibly integrated thermistor in the
motor is able to stop the frequency converter if the motor
overheats. The cut-out value is 3 kΩ.
1330
550
250
-20°C
175HA183.10
4000
3000
R
(Ω)
nominel
nominel -5°C
nominel +5°C
[°C]
Illustration 4.14 Resistance of a Thermistor
If a motor features a Klixon thermal switch instead, this
can also be connected to the input. If motors operate in
parallel, the thermistors/thermal switches can be
connected in series (total resistance lower than 3 kΩ).
Parameter 128 Motor thermal protection
must be set to
[1]
Thermistor warning
or
[2] Thermistor trip
and the thermistor
is to be connected between a digital input and terminal 50
(+10 V supply).
Illustration 4.15 Thermistor Connection
Select
Precise stop, inverse
to obtain a high degree of
accuracy when a stop command is repeated. A logic 0
means that the motor speed is ramped down to stop via
the selected ramp.
Select
Precise start/stop
to obtain a high degree of accuracy
when a start and stop command is repeated.
Select
Pulse reference
if the reference signal applied is a
pulse train (frequency). 0 Hz corresponds to
parameter 204
Minimum reference, Ref
MIN
. The frequency set in
parameter
327 Pulse reference/feedback
corresponds to
parameter 205
Maximum reference Ref
MAX
.
Select
Pulse feedback
if the feedback signal used is a pulse
train (frequency). In
parameter 327 Pulse reference/feedback
the maximum pulse feedback frequency is set.
Select
Pulse input
if a specific number of pulses must lead
to a
Precise stop
, see
parameter 343 Precise stop
and
parameter 344 Counter value
.
Selection of Setup, lsb
and
Selection of Setup, msb
give the
possibility to select one of the 4 setups. It is, however, a
condition that
parameter 004 Active Setup
is set to
[5]
Multisetup
.
Reset and start
can be used as a start function. If 24 V are
connected to the digital input, this causes the frequency
converter to reset and the motor ramps up to the preset
reference.
Pulse counter start
is used to start a counter stop sequence
with a pulse signal. The pulse width must at least be 14
ms and not longer than the count period. See also
parameter 343 Precise stop function
and the
VLT 2800
Precious Stop Instruction
.
308
Terminal 53, analog input voltage
Value:
No function (NO OPERATION)
[0]
Reference (reference)
[1]
Feedback (feedback)
[2]
Wobble (WOBB.DELTA FREQ [%])
[10]
Function:
Use this parameter to select the function required to be
connected to terminal 53. Scaling of the input signal is set
in
parameter 309 Terminal 53, min. scaling
and
parameter
310 Terminal 53, max. scaling
.
Description of choice:
Select
[0] No function
if the frequency converter is not to
react to signals connected to the terminal.
Programming