Description of choice:
Select the desired control word profile.
See
chapter 4.7 Serial communication
for further details of
control word profiles.
513
Bus time interval
Value:
1-99 s
1 s
Function:
Preset the maximum time expected to elapse between
receipt of 2 consecutive telegrams. If this time is exceeded,
the serial communication is assumed to have stopped and
the desired reaction is preset in
parameter 514 Bus time
interval function
.
Description of choice:
Preset the required time.
514
Bus time interval function
Value:
Off (off)
[0]
Freeze output frequency (FREEZE OUTPUT)
[1]
Stop (STOP)
[2]
Jogging (JOGGING)
[3]
Max. speed (MAX SPEED)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
Select the required reaction for the frequency converter
when the preset time in
parameter 513 Bus time interval
has been exceeded. If options
[1]
to
[5]
are activated, the
output relay is deactivated.
Description of choice:
The output frequency of the frequency converter can
•
be frozen at the present value,
•
stop the motor,
•
be frozen at parameter
213 Jogging frequency
,
•
be frozen at parameter
202 Output frequency, high
limit f
MAX
or
•
stop and activate a cut out.
Programming
Design Guide
120
Danfoss A/S © Rev. May/2014 All rights reserved.
MG27E402
4
4