3.4.17 Relay Connection
See
parameter 323 Relay output
for programming of relay output.
Nr.
01 - 02
1 - 2 make (normally open)
01 - 03 1 - 3 break (normally closed)
WARNING
The cable jacket for the relay must cover the first row of control card terminals. Otherwise the galvanic isolation (PELV)
cannot be maintained, which could result in equipment damage and personal injury. Maximum cable diameter is 4 mm.
Illustration 3.35 Relay Connection
3.4.18 Switches 1-4
The dip switch is only on the control card with Profibus DP
communication.
The switch position shown is the factory setting.
Switches 1 and 2 are used as cable termination for the
RS-485 interface. If the frequency converter is located as
the first or last unit in the bus system, switches 1 and 2
must be ON. On the remaining frequency converters,
switches 1 and 2 must be OFF.
Switches 3 and 4 are not applied.
3.4.19 VLT Motion Control Tool MCT 10
Set-up Software
Connection to terminals 68-70 or Sub D:
•
PIN 3 GND
•
PIN 8 P-RS 485
•
PIN 9 N-RS 485
Installation
Design Guide
MG27E402